🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 6.07V (2.53%)
Voltage at Load End233.1 VLoss: 6.9 V (3285.3 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A672.16 V (280.07%)0.0 V1108.75 V (461.98%)320158.1 WDrop/Amp High
12 AWG3.31 mm²20 A422.38 V (175.99%)0.0 V696.73 V (290.31%)201187.0 WDrop/Amp High
10 AWG5.26 mm²30 A265.8 V (110.75%)0.0 V438.44 V (182.68%)126602.5 WDrop/Amp High
8 AWG8.37 mm²50 A167.04 V (69.6%)73.0 V275.53 V (114.8%)79561.4 WDrop/Amp High
6 AWG13.3 mm²65 A105.12 V (43.8%)134.9 V173.4 V (72.25%)50069.8 WDrop/Amp High
4 AWG21.15 mm²85 A66.1 V (27.54%)173.9 V109.04 V (45.43%)31486.0 WDrop/Amp High
3 AWG26.67 mm²100 A52.42 V (21.84%)187.6 V86.47 V (36.03%)24969.2 WDrop/Amp High
2 AWG33.62 mm²115 A41.59 V (17.33%)198.4 V68.6 V (28.58%)19807.5 WDrop/Amp High
1 AWG42.41 mm²130 A32.97 V (13.74%)207.0 V54.38 V (22.66%)15702.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.14 V (10.89%)213.9 V43.11 V (17.96%)12449.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.73 V (8.64%)219.3 V34.2 V (14.25%)9875.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.45 V (6.85%)223.6 V27.13 V (11.3%)7833.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.04 V (5.43%)227.0 V21.51 V (8.96%)6212.0 WDrop/Amp High
250 kcmil126.7 mm²255 A11.03 V (4.6%)229.0 V18.2 V (7.58%)5256.0 WDrop/Amp High
300 kcmil152.0 mm²285 A9.2 V (3.83%)230.8 V15.17 V (6.32%)4381.1 W~ ≤5%
350 kcmil177.3 mm²310 A7.89 V (3.29%)232.1 V13.01 V (5.42%)3755.9 W~ ≤5%
400 kcmil202.7 mm²335 A6.9 V (2.87%)233.1 V11.38 V (4.74%)3285.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.52 V (2.3%)234.5 V9.1 V (3.79%)2628.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.6 V (1.92%)235.4 V7.59 V (3.16%)2190.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.68 V (1.53%)236.3 V6.07 V (2.53%)1752.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.76 V (1.15%)237.2 V4.55 V (1.9%)1314.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 450 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 6.9V (2.87%) and delivers 233.1V at the load.

What size aluminum wire is required for 275 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 6.07V (2.53%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.