🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.59V (3.16%)
Voltage at Load End233.9 VLoss: 6.13 V (2920.7 W)
Power & Breaker (125%)114.32 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1120.26 V (466.78%)0.0 V1847.91 V (769.96%)533596.9 WDrop/Amp High
12 AWG3.31 mm²20 A703.97 V (293.32%)0.0 V1161.22 V (483.84%)335311.7 WDrop/Amp High
10 AWG5.26 mm²30 A442.99 V (184.58%)0.0 V730.73 V (304.47%)211004.1 WDrop/Amp High
8 AWG8.37 mm²50 A278.39 V (116.0%)0.0 V459.22 V (191.34%)132602.3 WDrop/Amp High
6 AWG13.3 mm²65 A175.2 V (73.0%)64.8 V289.0 V (120.42%)83449.7 WDrop/Amp High
4 AWG21.15 mm²85 A110.17 V (45.91%)129.8 V181.73 V (75.72%)52476.7 WDrop/Amp High
3 AWG26.67 mm²100 A87.37 V (36.4%)152.6 V144.12 V (60.05%)41615.4 WDrop/Amp High
2 AWG33.62 mm²115 A69.31 V (28.88%)170.7 V114.33 V (47.64%)33012.5 WDrop/Amp High
1 AWG42.41 mm²130 A54.94 V (22.89%)185.1 V90.63 V (37.76%)26170.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A43.56 V (18.15%)196.4 V71.86 V (29.94%)20749.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A34.56 V (14.4%)205.4 V57.0 V (23.75%)16459.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.41 V (11.42%)212.6 V45.21 V (18.84%)13055.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.74 V (9.06%)218.3 V35.85 V (14.94%)10353.4 WDrop/Amp High
250 kcmil126.7 mm²255 A18.39 V (7.66%)221.6 V30.34 V (12.64%)8759.9 WDrop/Amp High
300 kcmil152.0 mm²285 A15.33 V (6.39%)224.7 V25.29 V (10.54%)7301.9 WDrop/Amp High
350 kcmil177.3 mm²310 A13.14 V (5.48%)226.9 V21.68 V (9.03%)6259.9 WDrop/Amp High
400 kcmil202.7 mm²335 A11.5 V (4.79%)228.5 V18.96 V (7.9%)5475.5 W~ ≤5%
500 kcmil253.4 mm²380 A9.2 V (3.83%)230.8 V15.17 V (6.32%)4380.0 W~ ≤5%
600 kcmil304.0 mm²420 A7.66 V (3.19%)232.3 V12.64 V (5.27%)3650.9 W~ ≤5%
750 kcmil380.0 mm²475 A6.13 V (2.55%)233.9 V10.11 V (4.21%)2920.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.6 V (1.92%)235.4 V7.59 V (3.16%)2190.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 750 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.13V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 275 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.59V (3.16%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.