🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)350 kcmil177.3 mm² · Drop: 0.8%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 4.41V (0.92%)
Voltage at Load End476.2 VLoss: 3.82 V (1986.6 W)
Power & Breaker (125%)249.42 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A325.89 V (67.89%)154.1 V537.57 V (111.99%)169339.8 WDrop/Amp High
12 AWG3.31 mm²20 A204.79 V (42.66%)275.2 V337.81 V (70.38%)106413.0 WDrop/Amp High
10 AWG5.26 mm²30 A128.87 V (26.85%)351.1 V212.58 V (44.29%)66963.3 WDrop/Amp High
8 AWG8.37 mm²50 A80.99 V (16.87%)399.0 V133.59 V (27.83%)42082.1 WDrop/Amp High
6 AWG13.3 mm²65 A50.97 V (10.62%)429.0 V84.07 V (17.51%)26483.2 WDrop/Amp High
4 AWG21.15 mm²85 A32.05 V (6.68%)447.9 V52.87 V (11.01%)16653.8 WDrop/Amp High
3 AWG26.67 mm²100 A25.42 V (5.3%)454.6 V41.93 V (8.73%)13206.9 WDrop/Amp High
2 AWG33.62 mm²115 A20.16 V (4.2%)459.8 V33.26 V (6.93%)10476.7 WDrop/Amp High
1 AWG42.41 mm²130 A15.98 V (3.33%)464.0 V26.37 V (5.49%)8305.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.67 V (2.64%)467.3 V20.9 V (4.35%)6584.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.05 V (2.09%)469.9 V16.58 V (3.45%)5223.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.97 V (1.66%)472.0 V13.15 V (2.74%)4143.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.32 V (1.32%)473.7 V10.43 V (2.17%)3285.7 WDrop/Amp High
250 kcmil126.7 mm²255 A5.35 V (1.11%)474.6 V8.83 V (1.84%)2780.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.46 V (0.93%)475.5 V7.36 V (1.53%)2317.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.82 V (0.8%)476.2 V6.31 V (1.31%)1986.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.34 V (0.7%)476.7 V5.52 V (1.15%)1737.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.68 V (0.56%)477.3 V4.41 V (0.92%)1390.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.23 V (0.46%)477.8 V3.68 V (0.77%)1158.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.78 V (0.37%)478.2 V2.94 V (0.61%)926.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.34 V (0.28%)478.7 V2.21 V (0.46%)695.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 200 feet one-way at 480V (3-Phase), you need 350 kcmil copper wire. This produces a voltage drop of 3.82V (0.8%) and delivers 476.2V at the load.

What size aluminum wire is required for 300 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 4.41V (0.92%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.