⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)6 AWGDrop: 11.21V (2.34%)
Voltage at Load End469.2 VLoss: 10.8 V (748.1 W)
Power & Breaker (125%)33.26 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A43.45 V (9.05%)436.5 V71.68 V (14.93%)3010.5 WDrop/Amp High
12 AWG3.31 mm²20 A27.31 V (5.69%)452.7 V45.04 V (9.38%)1891.8 WDrop/Amp High
10 AWG5.26 mm²30 A17.18 V (3.58%)462.8 V28.34 V (5.9%)1190.5 WDrop/Amp High
8 AWG8.37 mm²50 A10.8 V (2.25%)469.2 V17.81 V (3.71%)748.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A6.8 V (1.42%)473.2 V11.21 V (2.34%)470.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A4.27 V (0.89%)475.7 V7.05 V (1.47%)296.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A3.39 V (0.71%)476.6 V5.59 V (1.16%)234.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.69 V (0.56%)477.3 V4.43 V (0.92%)186.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.13 V (0.44%)477.9 V3.52 V (0.73%)147.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.69 V (0.35%)478.3 V2.79 V (0.58%)117.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.34 V (0.28%)478.7 V2.21 V (0.46%)92.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.06 V (0.22%)478.9 V1.75 V (0.37%)73.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.84 V (0.18%)479.2 V1.39 V (0.29%)58.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.71 V (0.15%)479.3 V1.18 V (0.25%)49.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.59 V (0.12%)479.4 V0.98 V (0.2%)41.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.51 V (0.11%)479.5 V0.84 V (0.18%)35.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.45 V (0.09%)479.6 V0.74 V (0.15%)30.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.36 V (0.07%)479.6 V0.59 V (0.12%)24.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.3 V (0.06%)479.7 V0.49 V (0.1%)20.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.24 V (0.05%)479.8 V0.39 V (0.08%)16.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.04%)479.8 V0.29 V (0.06%)12.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 200 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 10.8V (2.25%) and delivers 469.2V at the load.

What size aluminum wire is required for 40 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 11.21V (2.34%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.