🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.38%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.99V (0.42%)
Voltage at Load End478.2 VLoss: 1.81 V (1019.7 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A176.53 V (36.78%)303.5 V291.19 V (60.66%)99369.6 WDrop/Amp High
12 AWG3.31 mm²20 A110.93 V (23.11%)369.1 V182.98 V (38.12%)62443.7 WDrop/Amp High
10 AWG5.26 mm²30 A69.81 V (14.54%)410.2 V115.15 V (23.99%)39294.4 WDrop/Amp High
8 AWG8.37 mm²50 A43.87 V (9.14%)436.1 V72.36 V (15.08%)24694.0 WDrop/Amp High
6 AWG13.3 mm²65 A27.61 V (5.75%)452.4 V45.54 V (9.49%)15540.5 WDrop/Amp High
4 AWG21.15 mm²85 A17.36 V (3.62%)462.6 V28.64 V (5.97%)9772.5 WDrop/Amp High
3 AWG26.67 mm²100 A13.77 V (2.87%)466.2 V22.71 V (4.73%)7749.9 WDrop/Amp High
2 AWG33.62 mm²115 A10.92 V (2.28%)469.1 V18.02 V (3.75%)6147.8 WDrop/Amp High
1 AWG42.41 mm²130 A8.66 V (1.8%)471.3 V14.28 V (2.98%)4873.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.86 V (1.43%)473.1 V11.32 V (2.36%)3864.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.45 V (1.13%)474.6 V8.98 V (1.87%)3065.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.32 V (0.9%)475.7 V7.12 V (1.48%)2431.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.43 V (0.71%)476.6 V5.65 V (1.18%)1928.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.9 V (0.6%)477.1 V4.78 V (1.0%)1631.3 WDrop/Amp High
300 kcmil152.0 mm²285 A2.42 V (0.5%)477.6 V3.98 V (0.83%)1359.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.07 V (0.43%)477.9 V3.42 V (0.71%)1165.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.81 V (0.38%)478.2 V2.99 V (0.62%)1019.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.45 V (0.3%)478.6 V2.39 V (0.5%)815.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.21 V (0.25%)478.8 V1.99 V (0.42%)679.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.97 V (0.2%)479.0 V1.59 V (0.33%)543.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.72 V (0.15%)479.3 V1.2 V (0.25%)407.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 100 feet one-way at 480V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.81V (0.38%) and delivers 478.2V at the load.

What size aluminum wire is required for 325 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.99V (0.42%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.