🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 75 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 1.49V (0.31%)
Voltage at Load End478.6 VLoss: 1.36 V (764.8 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 75 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A132.39 V (27.58%)347.6 V218.39 V (45.5%)74527.2 WDrop/Amp High
12 AWG3.31 mm²20 A83.2 V (17.33%)396.8 V137.24 V (28.59%)46832.8 WDrop/Amp High
10 AWG5.26 mm²30 A52.35 V (10.91%)427.6 V86.36 V (17.99%)29470.8 WDrop/Amp High
8 AWG8.37 mm²50 A32.9 V (6.85%)447.1 V54.27 V (11.31%)18520.5 WDrop/Amp High
6 AWG13.3 mm²65 A20.71 V (4.31%)459.3 V34.15 V (7.12%)11655.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.02 V (2.71%)467.0 V21.48 V (4.47%)7329.4 WDrop/Amp High
3 AWG26.67 mm²100 A10.33 V (2.15%)469.7 V17.03 V (3.55%)5812.4 WDrop/Amp High
2 AWG33.62 mm²115 A8.19 V (1.71%)471.8 V13.51 V (2.81%)4610.8 WDrop/Amp High
1 AWG42.41 mm²130 A6.49 V (1.35%)473.5 V10.71 V (2.23%)3655.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.15 V (1.07%)474.9 V8.49 V (1.77%)2898.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.08 V (0.85%)475.9 V6.74 V (1.4%)2298.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.24 V (0.67%)476.8 V5.34 V (1.11%)1823.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.57 V (0.54%)477.4 V4.24 V (0.88%)1446.0 WDrop/Amp High
250 kcmil126.7 mm²255 A2.17 V (0.45%)477.8 V3.59 V (0.75%)1223.5 WDrop/Amp High
300 kcmil152.0 mm²285 A1.81 V (0.38%)478.2 V2.99 V (0.62%)1019.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.55 V (0.32%)478.4 V2.56 V (0.53%)874.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.36 V (0.28%)478.6 V2.24 V (0.47%)764.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.09 V (0.23%)478.9 V1.79 V (0.37%)611.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.91 V (0.19%)479.1 V1.49 V (0.31%)509.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.72 V (0.15%)479.3 V1.2 V (0.25%)407.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.54 V (0.11%)479.5 V0.9 V (0.19%)305.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 75 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 75 feet one-way at 480V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 1.36V (0.28%) and delivers 478.6V at the load.

What size aluminum wire is required for 325 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 1.49V (0.31%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.