🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 300 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.34%
Aluminum Wire (≤3% Drop)2 AWGDrop: 5.82V (2.43%)
Voltage at Load End234.4 VLoss: 5.61 V (340.0 W)
Power & Breaker (125%)14.55 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 300 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A57.03 V (23.76%)183.0 V94.08 V (39.2%)3457.4 WDrop/Amp High
12 AWG3.31 mm²20 A35.84 V (14.93%)204.2 V59.12 V (24.63%)2172.6 WDrop/Amp High
10 AWG5.26 mm²30 A22.55 V (9.4%)217.4 V37.2 V (15.5%)1367.2 WDrop/Amp High
8 AWG8.37 mm²50 A14.17 V (5.91%)225.8 V23.38 V (9.74%)859.2 WDrop/Amp High
6 AWG13.3 mm²65 A8.92 V (3.72%)231.1 V14.71 V (6.13%)540.7 W~ ≤5%
4 AWG21.15 mm²85 A5.61 V (2.34%)234.4 V9.25 V (3.85%)340.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.45 V (1.85%)235.6 V7.34 V (3.06%)269.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.53 V (1.47%)236.5 V5.82 V (2.43%)213.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.8 V (1.17%)237.2 V4.61 V (1.92%)169.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.22 V (0.92%)237.8 V3.66 V (1.52%)134.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.76 V (0.73%)238.2 V2.9 V (1.21%)106.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.4 V (0.58%)238.6 V2.3 V (0.96%)84.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.11 V (0.46%)238.9 V1.83 V (0.76%)67.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.94 V (0.39%)239.1 V1.54 V (0.64%)56.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.78 V (0.33%)239.2 V1.29 V (0.54%)47.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.67 V (0.28%)239.3 V1.1 V (0.46%)40.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.59 V (0.24%)239.4 V0.97 V (0.4%)35.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.47 V (0.2%)239.5 V0.77 V (0.32%)28.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.39 V (0.16%)239.6 V0.64 V (0.27%)23.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.31 V (0.13%)239.7 V0.51 V (0.21%)18.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.1%)239.8 V0.39 V (0.16%)14.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 300 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 300 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.61V (2.34%) and delivers 234.4V at the load.

What size aluminum wire is required for 35 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 5.82V (2.43%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.