🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.57%
Aluminum Wire (≤3% Drop)8 AWGDrop: 6.23V (2.6%)
Voltage at Load End236.2 VLoss: 3.78 V (229.1 W)
Power & Breaker (125%)14.55 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A15.21 V (6.34%)224.8 V25.09 V (10.45%)922.0 WDrop/Amp High
12 AWG3.31 mm²20 A9.56 V (3.98%)230.4 V15.76 V (6.57%)579.4 WDrop/Amp High
10 AWG5.26 mm²30 A6.01 V (2.51%)234.0 V9.92 V (4.13%)364.6 WDrop/Amp High
8 AWG8.37 mm²50 A3.78 V (1.57%)236.2 V6.23 V (2.6%)229.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.38 V (0.99%)237.6 V3.92 V (1.63%)144.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.5 V (0.62%)238.5 V2.47 V (1.03%)90.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.19 V (0.49%)238.8 V1.96 V (0.82%)71.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.94 V (0.39%)239.1 V1.55 V (0.65%)57.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.75 V (0.31%)239.3 V1.23 V (0.51%)45.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.59 V (0.25%)239.4 V0.98 V (0.41%)35.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.47 V (0.2%)239.5 V0.77 V (0.32%)28.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.37 V (0.16%)239.6 V0.61 V (0.26%)22.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.3 V (0.12%)239.7 V0.49 V (0.2%)17.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.25 V (0.1%)239.8 V0.41 V (0.17%)15.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.21 V (0.09%)239.8 V0.34 V (0.14%)12.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.18 V (0.07%)239.8 V0.29 V (0.12%)10.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.16 V (0.07%)239.8 V0.26 V (0.11%)9.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.05%)239.9 V0.21 V (0.09%)7.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.04%)239.9 V0.17 V (0.07%)6.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.03%)239.9 V0.14 V (0.06%)5.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.03%)239.9 V0.1 V (0.04%)3.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 80 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 3.78V (1.57%) and delivers 236.2V at the load.

What size aluminum wire is required for 35 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 6.23V (2.6%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.