🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 40 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.79%
Aluminum Wire (≤3% Drop)8 AWGDrop: 3.12V (1.3%)
Voltage at Load End238.1 VLoss: 1.89 V (114.6 W)
Power & Breaker (125%)14.55 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.6 V (3.17%)232.4 V12.54 V (5.23%)461.0 WDrop/Amp High
12 AWG3.31 mm²20 A4.78 V (1.99%)235.2 V7.88 V (3.28%)289.7 WDrop/Amp High
10 AWG5.26 mm²30 A3.01 V (1.25%)237.0 V4.96 V (2.07%)182.3 WDrop/Amp High
8 AWG8.37 mm²50 A1.89 V (0.79%)238.1 V3.12 V (1.3%)114.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.19 V (0.5%)238.8 V1.96 V (0.82%)72.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.75 V (0.31%)239.3 V1.23 V (0.51%)45.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.59 V (0.25%)239.4 V0.98 V (0.41%)36.0 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.47 V (0.2%)239.5 V0.78 V (0.32%)28.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.37 V (0.16%)239.6 V0.62 V (0.26%)22.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.3 V (0.12%)239.7 V0.49 V (0.2%)17.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.23 V (0.1%)239.8 V0.39 V (0.16%)14.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.19 V (0.08%)239.8 V0.31 V (0.13%)11.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.15 V (0.06%)239.9 V0.24 V (0.1%)8.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.12 V (0.05%)239.9 V0.21 V (0.09%)7.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.1 V (0.04%)239.9 V0.17 V (0.07%)6.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.04%)239.9 V0.15 V (0.06%)5.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.03%)239.9 V0.13 V (0.05%)4.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.03%)239.9 V0.1 V (0.04%)3.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.02%)239.9 V0.09 V (0.04%)3.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.02%)240.0 V0.07 V (0.03%)2.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)240.0 V0.05 V (0.02%)1.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 40 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 1.89V (0.79%) and delivers 238.1V at the load.

What size aluminum wire is required for 35 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 3.12V (1.3%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.