⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 0.42%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 2.07V (0.43%)
Voltage at Load End478.0 VLoss: 2.0 V (432.6 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.74 V (8.49%)439.3 V67.2 V (14.0%)8819.8 WDrop/Amp High
12 AWG3.31 mm²20 A25.6 V (5.33%)454.4 V42.23 V (8.8%)5542.3 WDrop/Amp High
10 AWG5.26 mm²30 A16.11 V (3.36%)463.9 V26.57 V (5.54%)3487.7 WDrop/Amp High
8 AWG8.37 mm²50 A10.12 V (2.11%)469.9 V16.7 V (3.48%)2191.8 WDrop/Amp High
6 AWG13.3 mm²65 A6.37 V (1.33%)473.6 V10.51 V (2.19%)1379.3 WDrop/Amp High
4 AWG21.15 mm²85 A4.01 V (0.83%)476.0 V6.61 V (1.38%)867.4 WDrop/Amp High
3 AWG26.67 mm²100 A3.18 V (0.66%)476.8 V5.24 V (1.09%)687.9 WDrop/Amp High
2 AWG33.62 mm²115 A2.52 V (0.53%)477.5 V4.16 V (0.87%)545.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.0 V (0.42%)478.0 V3.3 V (0.69%)432.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.58 V (0.33%)478.4 V2.61 V (0.54%)343.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.26 V (0.26%)478.7 V2.07 V (0.43%)272.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.0 V (0.21%)479.0 V1.64 V (0.34%)215.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.79 V (0.16%)479.2 V1.3 V (0.27%)171.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.67 V (0.14%)479.3 V1.1 V (0.23%)144.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.56 V (0.12%)479.4 V0.92 V (0.19%)120.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.48 V (0.1%)479.5 V0.79 V (0.16%)103.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.42 V (0.09%)479.6 V0.69 V (0.14%)90.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.33 V (0.07%)479.7 V0.55 V (0.11%)72.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.28 V (0.06%)479.7 V0.46 V (0.1%)60.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (0.05%)479.8 V0.37 V (0.08%)48.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (0.03%)479.8 V0.28 V (0.06%)36.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 60 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 2.0V (0.42%) and delivers 478.0V at the load.

What size aluminum wire is required for 125 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 2.07V (0.43%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.