⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.53%
Aluminum Wire (≤3% Drop)2 AWGDrop: 2.66V (0.55%)
Voltage at Load End477.4 VLoss: 2.56 V (355.3 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A26.07 V (5.43%)453.9 V43.01 V (8.96%)3612.6 WDrop/Amp High
12 AWG3.31 mm²20 A16.38 V (3.41%)463.6 V27.02 V (5.63%)2270.1 WDrop/Amp High
10 AWG5.26 mm²30 A10.31 V (2.15%)469.7 V17.01 V (3.54%)1428.6 WDrop/Amp High
8 AWG8.37 mm²50 A6.48 V (1.35%)473.5 V10.69 V (2.23%)897.8 WDrop/Amp High
6 AWG13.3 mm²65 A4.08 V (0.85%)475.9 V6.73 V (1.4%)565.0 WDrop/Amp High
4 AWG21.15 mm²85 A2.56 V (0.53%)477.4 V4.23 V (0.88%)355.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.03 V (0.42%)478.0 V3.35 V (0.7%)281.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.61 V (0.34%)478.4 V2.66 V (0.55%)223.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.28 V (0.27%)478.7 V2.11 V (0.44%)177.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.01 V (0.21%)479.0 V1.67 V (0.35%)140.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.8 V (0.17%)479.2 V1.33 V (0.28%)111.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.64 V (0.13%)479.4 V1.05 V (0.22%)88.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.51 V (0.11%)479.5 V0.83 V (0.17%)70.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.43 V (0.09%)479.6 V0.71 V (0.15%)59.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.36 V (0.07%)479.6 V0.59 V (0.12%)49.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.31 V (0.06%)479.7 V0.5 V (0.11%)42.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.27 V (0.06%)479.7 V0.44 V (0.09%)37.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.21 V (0.04%)479.8 V0.35 V (0.07%)29.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.18 V (0.04%)479.8 V0.29 V (0.06%)24.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (0.03%)479.9 V0.24 V (0.05%)19.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.02%)479.9 V0.18 V (0.04%)14.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 60 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 2.56V (0.53%) and delivers 477.4V at the load.

What size aluminum wire is required for 80 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 2.66V (0.55%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.