🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 30 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.45%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.59V (0.5%)
Voltage at Load End119.5 VLoss: 0.54 V (189.2 W)
Power & Breaker (125%)42.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 30 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A65.85 V (54.88%)54.1 V108.63 V (90.52%)23049.0 WDrop/Amp High
12 AWG3.31 mm²20 A41.38 V (34.49%)78.6 V68.26 V (56.89%)14484.0 WDrop/Amp High
10 AWG5.26 mm²30 A26.04 V (21.7%)94.0 V42.96 V (35.8%)9114.4 WDrop/Amp High
8 AWG8.37 mm²50 A16.37 V (13.64%)103.6 V27.0 V (22.5%)5727.8 WDrop/Amp High
6 AWG13.3 mm²65 A10.3 V (8.58%)109.7 V16.99 V (14.16%)3604.7 WDrop/Amp High
4 AWG21.15 mm²85 A6.48 V (5.4%)113.5 V10.68 V (8.9%)2266.8 WDrop/Amp High
3 AWG26.67 mm²100 A5.14 V (4.28%)114.9 V8.47 V (7.06%)1797.6 WDrop/Amp High
2 AWG33.62 mm²115 A4.07 V (3.4%)115.9 V6.72 V (5.6%)1426.0 WDrop/Amp High
1 AWG42.41 mm²130 A3.23 V (2.69%)116.8 V5.33 V (4.44%)1130.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.56 V (2.13%)117.4 V4.22 V (3.52%)896.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.03 V (1.69%)118.0 V3.35 V (2.79%)711.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.61 V (1.34%)118.4 V2.66 V (2.21%)564.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.28 V (1.06%)118.7 V2.11 V (1.76%)447.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.08 V (0.9%)118.9 V1.78 V (1.49%)378.4 WDrop/Amp High
300 kcmil152.0 mm²285 A0.9 V (0.75%)119.1 V1.49 V (1.24%)315.4 WDrop/Amp High
350 kcmil177.3 mm²310 A0.77 V (0.64%)119.2 V1.27 V (1.06%)270.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.68 V (0.56%)119.3 V1.11 V (0.93%)236.5 WDrop/Amp High
500 kcmil253.4 mm²380 A0.54 V (0.45%)119.5 V0.89 V (0.74%)189.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.45 V (0.38%)119.5 V0.74 V (0.62%)157.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.36 V (0.3%)119.6 V0.59 V (0.5%)126.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.27 V (0.23%)119.7 V0.45 V (0.37%)94.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 30 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 30 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 0.54V (0.45%) and delivers 119.5V at the load.

What size aluminum wire is required for 350 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.59V (0.5%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.