⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.88%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 2.48V (2.06%)
Voltage at Load End117.7 VLoss: 2.25 V (788.3 W)
Power & Breaker (125%)42.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A274.39 V (228.66%)0.0 V452.62 V (377.18%)96037.6 WDrop/Amp High
12 AWG3.31 mm²20 A172.43 V (143.69%)0.0 V284.43 V (237.02%)60349.9 WDrop/Amp High
10 AWG5.26 mm²30 A108.51 V (90.42%)11.5 V178.98 V (149.15%)37976.9 WDrop/Amp High
8 AWG8.37 mm²50 A68.19 V (56.82%)51.8 V112.48 V (93.73%)23866.0 WDrop/Amp High
6 AWG13.3 mm²65 A42.91 V (35.76%)77.1 V70.79 V (58.99%)15019.4 WDrop/Amp High
4 AWG21.15 mm²85 A26.99 V (22.49%)93.0 V44.51 V (37.09%)9444.8 WDrop/Amp High
3 AWG26.67 mm²100 A21.4 V (17.83%)98.6 V35.3 V (29.42%)7490.0 WDrop/Amp High
2 AWG33.62 mm²115 A16.98 V (14.15%)103.0 V28.0 V (23.34%)5941.7 WDrop/Amp High
1 AWG42.41 mm²130 A13.46 V (11.21%)106.5 V22.2 V (18.5%)4710.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.67 V (8.89%)109.3 V17.6 V (14.67%)3734.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.46 V (7.05%)111.5 V13.96 V (11.63%)2962.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.71 V (5.59%)113.3 V11.07 V (9.23%)2349.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.32 V (4.44%)114.7 V8.78 V (7.32%)1863.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.5 V (3.75%)115.5 V7.43 V (6.19%)1576.6 WDrop/Amp High
300 kcmil152.0 mm²285 A3.75 V (3.13%)116.2 V6.19 V (5.16%)1314.2 WDrop/Amp High
350 kcmil177.3 mm²310 A3.22 V (2.68%)116.8 V5.31 V (4.42%)1126.7 WDrop/Amp High
400 kcmil202.7 mm²335 A2.82 V (2.35%)117.2 V4.64 V (3.87%)985.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.25 V (1.88%)117.7 V3.72 V (3.1%)788.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.88 V (1.56%)118.1 V3.1 V (2.58%)657.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.5 V (1.25%)118.5 V2.48 V (2.06%)525.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.94%)118.9 V1.86 V (1.55%)394.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 125 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.25V (1.88%) and delivers 117.7V at the load.

What size aluminum wire is required for 350 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 2.48V (2.06%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.