🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.75%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.99V (0.83%)
Voltage at Load End119.1 VLoss: 0.9 V (315.3 W)
Power & Breaker (125%)42.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A109.76 V (91.46%)10.2 V181.05 V (150.87%)38415.1 WDrop/Amp High
12 AWG3.31 mm²20 A68.97 V (57.48%)51.0 V113.77 V (94.81%)24140.0 WDrop/Amp High
10 AWG5.26 mm²30 A43.4 V (36.17%)76.6 V71.59 V (59.66%)15190.7 WDrop/Amp High
8 AWG8.37 mm²50 A27.28 V (22.73%)92.7 V44.99 V (37.49%)9546.4 WDrop/Amp High
6 AWG13.3 mm²65 A17.17 V (14.3%)102.8 V28.31 V (23.6%)6007.8 WDrop/Amp High
4 AWG21.15 mm²85 A10.79 V (9.0%)109.2 V17.81 V (14.84%)3777.9 WDrop/Amp High
3 AWG26.67 mm²100 A8.56 V (7.13%)111.4 V14.12 V (11.77%)2996.0 WDrop/Amp High
2 AWG33.62 mm²115 A6.79 V (5.66%)113.2 V11.2 V (9.33%)2376.7 WDrop/Amp High
1 AWG42.41 mm²130 A5.38 V (4.49%)114.6 V8.88 V (7.4%)1884.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.27 V (3.56%)115.7 V7.04 V (5.87%)1493.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.39 V (2.82%)116.6 V5.58 V (4.65%)1185.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.69 V (2.24%)117.3 V4.43 V (3.69%)939.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.13 V (1.77%)117.9 V3.51 V (2.93%)745.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.8 V (1.5%)118.2 V2.97 V (2.48%)630.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.5 V (1.25%)118.5 V2.48 V (2.06%)525.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.29 V (1.07%)118.7 V2.12 V (1.77%)450.7 WDrop/Amp High
400 kcmil202.7 mm²335 A1.13 V (0.94%)118.9 V1.86 V (1.55%)394.2 WDrop/Amp High
500 kcmil253.4 mm²380 A0.9 V (0.75%)119.1 V1.49 V (1.24%)315.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.75 V (0.63%)119.2 V1.24 V (1.03%)262.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.6 V (0.5%)119.4 V0.99 V (0.83%)210.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.45 V (0.38%)119.5 V0.74 V (0.62%)157.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 50 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 0.9V (0.75%) and delivers 119.1V at the load.

What size aluminum wire is required for 350 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.99V (0.83%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.