🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 450 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.79V (2.78%)
Voltage at Load End202.1 VLoss: 5.85 V (3548.3 W)
Power & Breaker (125%)126.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 450 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A855.47 V (411.29%)0.0 V1411.13 V (678.43%)518603.3 WDrop/Amp High
12 AWG3.31 mm²20 A537.58 V (258.45%)0.0 V886.75 V (426.32%)325889.7 WDrop/Amp High
10 AWG5.26 mm²30 A338.29 V (162.64%)0.0 V558.01 V (268.28%)205075.1 WDrop/Amp High
8 AWG8.37 mm²50 A212.59 V (102.21%)0.0 V350.68 V (168.59%)128876.3 WDrop/Amp High
6 AWG13.3 mm²65 A133.79 V (64.32%)74.2 V220.69 V (106.1%)81104.9 WDrop/Amp High
4 AWG21.15 mm²85 A84.13 V (40.45%)123.9 V138.78 V (66.72%)51002.1 WDrop/Amp High
3 AWG26.67 mm²100 A66.72 V (32.08%)141.3 V110.05 V (52.91%)40446.0 WDrop/Amp High
2 AWG33.62 mm²115 A52.93 V (25.45%)155.1 V87.3 V (41.97%)32084.9 WDrop/Amp High
1 AWG42.41 mm²130 A41.96 V (20.17%)166.0 V69.21 V (33.27%)25434.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A33.27 V (15.99%)174.7 V54.87 V (26.38%)20166.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.39 V (12.69%)181.6 V43.53 V (20.93%)15997.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.93 V (10.06%)187.1 V34.53 V (16.6%)12689.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.6 V (7.98%)191.4 V27.38 V (13.16%)10062.5 WDrop/Amp High
250 kcmil126.7 mm²255 A14.04 V (6.75%)194.0 V23.17 V (11.14%)8513.8 WDrop/Amp High
300 kcmil152.0 mm²285 A11.71 V (5.63%)196.3 V19.31 V (9.28%)7096.7 WDrop/Amp High
350 kcmil177.3 mm²310 A10.04 V (4.83%)198.0 V16.55 V (7.96%)6084.0 WDrop/Amp High
400 kcmil202.7 mm²335 A8.78 V (4.22%)199.2 V14.48 V (6.96%)5321.6 WDrop/Amp High
500 kcmil253.4 mm²380 A7.02 V (3.38%)201.0 V11.58 V (5.57%)4256.9 W~ ≤5%
600 kcmil304.0 mm²420 A5.85 V (2.81%)202.1 V9.66 V (4.64%)3548.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.68 V (2.25%)203.3 V7.72 V (3.71%)2838.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.51 V (1.69%)204.5 V5.79 V (2.78%)2128.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 450 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 450 feet one-way at 208V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 5.85V (2.81%) and delivers 202.1V at the load.

What size aluminum wire is required for 350 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.79V (2.78%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.