🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)16× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.92V (74.32%)
Voltage at Load End11.7 VLoss: 0.34 V (118.3 W)
Power & Breaker (125%)4.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1317.09 V (10975.73%)0.0 V2172.58 V (18104.83%)460980.7 WDrop/Amp High
12 AWG3.31 mm²20 A827.66 V (6897.14%)0.0 V1365.25 V (11377.05%)289679.7 WDrop/Amp High
10 AWG5.26 mm²30 A520.83 V (4340.21%)0.0 V859.12 V (7159.32%)182288.9 WDrop/Amp High
8 AWG8.37 mm²50 A327.3 V (2727.54%)0.0 V539.9 V (4499.17%)114556.7 WDrop/Amp High
6 AWG13.3 mm²65 A205.98 V (1716.51%)0.0 V339.77 V (2831.43%)72093.2 WDrop/Amp High
4 AWG21.15 mm²85 A129.53 V (1079.41%)0.0 V213.66 V (1780.52%)45335.2 WDrop/Amp High
3 AWG26.67 mm²100 A102.72 V (856.0%)0.0 V169.44 V (1412.0%)35952.0 WDrop/Amp High
2 AWG33.62 mm²115 A81.49 V (679.05%)0.0 V134.41 V (1120.11%)28519.9 WDrop/Amp High
1 AWG42.41 mm²130 A64.6 V (538.31%)0.0 V106.55 V (887.95%)22608.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A51.22 V (426.8%)0.0 V84.48 V (704.02%)17925.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A40.63 V (338.57%)0.0 V67.02 V (558.48%)14219.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.23 V (268.55%)0.0 V53.16 V (442.98%)11279.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.56 V (212.96%)0.0 V42.15 V (351.29%)8944.4 WDrop/Amp High
250 kcmil126.7 mm²255 A21.62 V (180.19%)0.0 V35.67 V (297.22%)7567.8 WDrop/Amp High
300 kcmil152.0 mm²285 A18.02 V (150.19%)0.0 V29.73 V (247.75%)6308.2 WDrop/Amp High
350 kcmil177.3 mm²310 A15.45 V (128.76%)0.0 V25.49 V (212.4%)5408.0 WDrop/Amp High
400 kcmil202.7 mm²335 A13.52 V (112.63%)0.0 V22.29 V (185.78%)4730.3 WDrop/Amp High
500 kcmil253.4 mm²380 A10.81 V (90.09%)1.2 V17.83 V (148.61%)3783.9 WDrop/Amp High
600 kcmil304.0 mm²420 A9.01 V (75.1%)3.0 V14.87 V (123.88%)3154.1 WDrop/Amp High
750 kcmil380.0 mm²475 A7.21 V (60.08%)4.8 V11.89 V (99.1%)2523.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.41 V (45.06%)6.6 V8.92 V (74.32%)1892.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 600 feet one-way at 12V (DC), you need 16× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 350 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.92V (74.32%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.