⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.79V (2.32%)
Voltage at Load End116.6 VLoss: 3.38 V (1266.9 W)
Power & Breaker (125%)45.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A411.59 V (342.99%)0.0 V678.93 V (565.78%)154346.2 WDrop/Amp High
12 AWG3.31 mm²20 A258.64 V (215.54%)0.0 V426.64 V (355.53%)96991.0 WDrop/Amp High
10 AWG5.26 mm²30 A162.76 V (135.63%)0.0 V268.47 V (223.73%)61034.2 WDrop/Amp High
8 AWG8.37 mm²50 A102.28 V (85.24%)17.7 V168.72 V (140.6%)38356.0 WDrop/Amp High
6 AWG13.3 mm²65 A64.37 V (53.64%)55.6 V106.18 V (88.48%)24138.4 WDrop/Amp High
4 AWG21.15 mm²85 A40.48 V (33.73%)79.5 V66.77 V (55.64%)15179.2 WDrop/Amp High
3 AWG26.67 mm²100 A32.1 V (26.75%)87.9 V52.95 V (44.12%)12037.5 WDrop/Amp High
2 AWG33.62 mm²115 A25.46 V (21.22%)94.5 V42.0 V (35.0%)9549.1 WDrop/Amp High
1 AWG42.41 mm²130 A20.19 V (16.82%)99.8 V33.3 V (27.75%)7569.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.0 V (13.34%)104.0 V26.4 V (22.0%)6001.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.7 V (10.58%)107.3 V20.94 V (17.45%)4761.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.07 V (8.39%)109.9 V16.61 V (13.84%)3776.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.99 V (6.66%)112.0 V13.17 V (10.98%)2994.8 WDrop/Amp High
250 kcmil126.7 mm²255 A6.76 V (5.63%)113.2 V11.15 V (9.29%)2533.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.63 V (4.69%)114.4 V9.29 V (7.74%)2112.1 WDrop/Amp High
350 kcmil177.3 mm²310 A4.83 V (4.02%)115.2 V7.96 V (6.64%)1810.7 WDrop/Amp High
400 kcmil202.7 mm²335 A4.22 V (3.52%)115.8 V6.97 V (5.81%)1583.8 WDrop/Amp High
500 kcmil253.4 mm²380 A3.38 V (2.82%)116.6 V5.57 V (4.64%)1266.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.82 V (2.35%)117.2 V4.65 V (3.87%)1056.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.25 V (1.88%)117.7 V3.72 V (3.1%)844.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.69 V (1.41%)118.3 V2.79 V (2.32%)633.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 175 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.38V (2.82%) and delivers 116.6V at the load.

What size aluminum wire is required for 375 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.79V (2.32%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.