🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 2.65V (2.21%)
Voltage at Load End117.6 VLoss: 2.41 V (905.0 W)
Power & Breaker (125%)45.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A293.99 V (244.99%)0.0 V484.95 V (404.13%)110247.3 WDrop/Amp High
12 AWG3.31 mm²20 A184.74 V (153.95%)0.0 V304.74 V (253.95%)69279.3 WDrop/Amp High
10 AWG5.26 mm²30 A116.26 V (96.88%)3.7 V191.77 V (159.81%)43595.9 WDrop/Amp High
8 AWG8.37 mm²50 A73.06 V (60.88%)46.9 V120.51 V (100.43%)27397.2 WDrop/Amp High
6 AWG13.3 mm²65 A45.98 V (38.31%)74.0 V75.84 V (63.2%)17241.7 WDrop/Amp High
4 AWG21.15 mm²85 A28.91 V (24.09%)91.1 V47.69 V (39.74%)10842.3 WDrop/Amp High
3 AWG26.67 mm²100 A22.93 V (19.11%)97.1 V37.82 V (31.52%)8598.2 WDrop/Amp High
2 AWG33.62 mm²115 A18.19 V (15.16%)101.8 V30.0 V (25.0%)6820.8 WDrop/Amp High
1 AWG42.41 mm²130 A14.42 V (12.02%)105.6 V23.78 V (19.82%)5407.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.43 V (9.53%)108.6 V18.86 V (15.71%)4287.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.07 V (7.56%)110.9 V14.96 V (12.47%)3400.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.19 V (5.99%)112.8 V11.87 V (9.89%)2697.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.7 V (4.75%)114.3 V9.41 V (7.84%)2139.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.83 V (4.02%)115.2 V7.96 V (6.63%)1809.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.02 V (3.35%)116.0 V6.64 V (5.53%)1508.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.45 V (2.87%)116.6 V5.69 V (4.74%)1293.4 WDrop/Amp High
400 kcmil202.7 mm²335 A3.02 V (2.51%)117.0 V4.98 V (4.15%)1131.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.41 V (2.01%)117.6 V3.98 V (3.32%)905.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.01 V (1.68%)118.0 V3.32 V (2.77%)754.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.61 V (1.34%)118.4 V2.65 V (2.21%)603.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.21 V (1.01%)118.8 V1.99 V (1.66%)452.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 125 feet one-way at 120V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.41V (2.01%) and delivers 117.6V at the load.

What size aluminum wire is required for 375 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 2.65V (2.21%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.