🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.57%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.14V (1.72%)
Voltage at Load End236.2 VLoss: 3.76 V (2443.4 W)
Power & Breaker (125%)155.88 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A458.29 V (190.95%)0.0 V755.96 V (314.98%)297667.7 WDrop/Amp High
12 AWG3.31 mm²20 A287.99 V (120.0%)0.0 V475.05 V (197.94%)187054.0 WDrop/Amp High
10 AWG5.26 mm²30 A181.22 V (75.51%)58.8 V298.94 V (124.56%)117708.9 WDrop/Amp High
8 AWG8.37 mm²50 A113.89 V (47.45%)126.1 V187.86 V (78.28%)73972.4 WDrop/Amp High
6 AWG13.3 mm²65 A71.67 V (29.86%)168.3 V118.23 V (49.26%)46552.5 WDrop/Amp High
4 AWG21.15 mm²85 A45.07 V (18.78%)194.9 V74.35 V (30.98%)29274.2 WDrop/Amp High
3 AWG26.67 mm²100 A35.74 V (14.89%)204.3 V58.96 V (24.57%)23215.2 WDrop/Amp High
2 AWG33.62 mm²115 A28.35 V (11.81%)211.6 V46.77 V (19.49%)18416.1 WDrop/Amp High
1 AWG42.41 mm²130 A22.48 V (9.37%)217.5 V37.08 V (15.45%)14599.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.82 V (7.43%)222.2 V29.4 V (12.25%)11575.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.14 V (5.89%)225.9 V23.32 V (9.72%)9182.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.21 V (4.67%)228.8 V18.5 V (7.71%)7283.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.89 V (3.71%)231.1 V14.67 V (6.11%)5775.6 WDrop/Amp High
250 kcmil126.7 mm²255 A7.52 V (3.13%)232.5 V12.41 V (5.17%)4886.7 WDrop/Amp High
300 kcmil152.0 mm²285 A6.27 V (2.61%)233.7 V10.34 V (4.31%)4073.3 WDrop/Amp High
350 kcmil177.3 mm²310 A5.38 V (2.24%)234.6 V8.87 V (3.7%)3492.1 WDrop/Amp High
400 kcmil202.7 mm²335 A4.7 V (1.96%)235.3 V7.76 V (3.23%)3054.5 WDrop/Amp High
500 kcmil253.4 mm²380 A3.76 V (1.57%)236.2 V6.21 V (2.59%)2443.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.14 V (1.31%)236.9 V5.17 V (2.16%)2036.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.51 V (1.05%)237.5 V4.14 V (1.72%)1629.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.88 V (0.78%)238.1 V3.1 V (1.29%)1221.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 225 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.76V (1.57%) and delivers 236.2V at the load.

What size aluminum wire is required for 375 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.14V (1.72%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.