375 Amp Wire Size at 350 Feet (480V Three-Phase (US Heavy Industrial))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 350 ft (106.7 m) one-way run.
Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.22%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 6.44V (1.34%)
Voltage at Load End474.1 VLoss: 5.85 V (3800.8 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended
All AWG & kcmil Wire Gauges for 375 Amps at 350 Feet (480V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 712.89 V (148.52%) | 0.0 V | 1175.94 V (244.99%) | 463038.6 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 447.98 V (93.33%) | 32.0 V | 738.96 V (153.95%) | 290972.9 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 281.91 V (58.73%) | 198.1 V | 465.01 V (96.88%) | 183102.7 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 177.16 V (36.91%) | 302.8 V | 292.23 V (60.88%) | 115068.1 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 111.49 V (23.23%) | 368.5 V | 183.91 V (38.31%) | 72415.1 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 70.11 V (14.61%) | 409.9 V | 115.65 V (24.09%) | 45537.6 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 55.6 V (11.58%) | 424.4 V | 91.71 V (19.11%) | 36112.5 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 44.11 V (9.19%) | 435.9 V | 72.75 V (15.16%) | 28647.2 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 34.96 V (7.28%) | 445.0 V | 57.67 V (12.02%) | 22709.7 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 27.72 V (5.78%) | 452.3 V | 45.73 V (9.53%) | 18005.6 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 21.99 V (4.58%) | 458.0 V | 36.27 V (7.56%) | 14283.3 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 17.44 V (3.63%) | 462.6 V | 28.77 V (5.99%) | 11329.5 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 13.83 V (2.88%) | 466.2 V | 22.82 V (4.75%) | 8984.3 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 11.7 V (2.44%) | 468.3 V | 19.31 V (4.02%) | 7601.6 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 9.76 V (2.03%) | 470.2 V | 16.09 V (3.35%) | 6336.3 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 8.36 V (1.74%) | 471.6 V | 13.8 V (2.87%) | 5432.2 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 7.32 V (1.52%) | 472.7 V | 12.07 V (2.51%) | 4751.5 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 5.85 V (1.22%) | 474.1 V | 9.65 V (2.01%) | 3800.8 W | ✓ PASS (≤3%) |
| 600 kcmil | 304.0 mm² | 420 A | 4.88 V (1.02%) | 475.1 V | 8.05 V (1.68%) | 3168.2 W | ✓ PASS (≤3%) |
| 750 kcmil | 380.0 mm² | 475 A | 3.9 V (0.81%) | 476.1 V | 6.44 V (1.34%) | 2534.5 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 2.93 V (0.61%) | 477.1 V | 4.83 V (1.01%) | 1900.8 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 375 amps at 350 feet (480V)?
To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 350 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 5.85V (1.22%) and delivers 474.1V at the load.
What size aluminum wire is required for 375 amps at 350 feet?
Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 6.44V (1.34%).
What breaker size is needed for a 375A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.