🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.44%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 2.3V (0.48%)
Voltage at Load End477.9 VLoss: 2.09 V (1357.4 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A254.61 V (53.04%)225.4 V419.98 V (87.5%)165370.9 WDrop/Amp High
12 AWG3.31 mm²20 A159.99 V (33.33%)320.0 V263.91 V (54.98%)103918.9 WDrop/Amp High
10 AWG5.26 mm²30 A100.68 V (20.98%)379.3 V166.08 V (34.6%)65393.8 WDrop/Amp High
8 AWG8.37 mm²50 A63.27 V (13.18%)416.7 V104.37 V (21.74%)41095.8 WDrop/Amp High
6 AWG13.3 mm²65 A39.82 V (8.3%)440.2 V65.68 V (13.68%)25862.5 WDrop/Amp High
4 AWG21.15 mm²85 A25.04 V (5.22%)455.0 V41.3 V (8.6%)16263.4 WDrop/Amp High
3 AWG26.67 mm²100 A19.86 V (4.14%)460.1 V32.75 V (6.82%)12897.3 WDrop/Amp High
2 AWG33.62 mm²115 A15.75 V (3.28%)464.2 V25.98 V (5.41%)10231.2 WDrop/Amp High
1 AWG42.41 mm²130 A12.49 V (2.6%)467.5 V20.6 V (4.29%)8110.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.9 V (2.06%)470.1 V16.33 V (3.4%)6430.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.85 V (1.64%)472.1 V12.96 V (2.7%)5101.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.23 V (1.3%)473.8 V10.28 V (2.14%)4046.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.94 V (1.03%)475.1 V8.15 V (1.7%)3208.7 WDrop/Amp High
250 kcmil126.7 mm²255 A4.18 V (0.87%)475.8 V6.89 V (1.44%)2714.9 WDrop/Amp High
300 kcmil152.0 mm²285 A3.48 V (0.73%)476.5 V5.75 V (1.2%)2263.0 WDrop/Amp High
350 kcmil177.3 mm²310 A2.99 V (0.62%)477.0 V4.93 V (1.03%)1940.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.61 V (0.54%)477.4 V4.31 V (0.9%)1696.9 WDrop/Amp High
500 kcmil253.4 mm²380 A2.09 V (0.44%)477.9 V3.45 V (0.72%)1357.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.74 V (0.36%)478.3 V2.87 V (0.6%)1131.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.39 V (0.29%)478.6 V2.3 V (0.48%)905.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.05 V (0.22%)479.0 V1.72 V (0.36%)678.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 125 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 2.09V (0.44%) and delivers 477.9V at the load.

What size aluminum wire is required for 375 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 2.3V (0.48%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.