🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 75 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.26%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 1.38V (0.29%)
Voltage at Load End478.7 VLoss: 1.25 V (814.5 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 75 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.76 V (31.83%)327.2 V251.99 V (52.5%)99222.6 WDrop/Amp High
12 AWG3.31 mm²20 A96.0 V (20.0%)384.0 V158.35 V (32.99%)62351.3 WDrop/Amp High
10 AWG5.26 mm²30 A60.41 V (12.59%)419.6 V99.65 V (20.76%)39236.3 WDrop/Amp High
8 AWG8.37 mm²50 A37.96 V (7.91%)442.0 V62.62 V (13.05%)24657.5 WDrop/Amp High
6 AWG13.3 mm²65 A23.89 V (4.98%)456.1 V39.41 V (8.21%)15517.5 WDrop/Amp High
4 AWG21.15 mm²85 A15.02 V (3.13%)465.0 V24.78 V (5.16%)9758.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.91 V (2.48%)468.1 V19.65 V (4.09%)7738.4 WDrop/Amp High
2 AWG33.62 mm²115 A9.45 V (1.97%)470.5 V15.59 V (3.25%)6138.7 WDrop/Amp High
1 AWG42.41 mm²130 A7.49 V (1.56%)472.5 V12.36 V (2.57%)4866.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.94 V (1.24%)474.1 V9.8 V (2.04%)3858.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.71 V (0.98%)475.3 V7.77 V (1.62%)3060.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.74 V (0.78%)476.3 V6.17 V (1.28%)2427.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.96 V (0.62%)477.0 V4.89 V (1.02%)1925.2 WDrop/Amp High
250 kcmil126.7 mm²255 A2.51 V (0.52%)477.5 V4.14 V (0.86%)1628.9 WDrop/Amp High
300 kcmil152.0 mm²285 A2.09 V (0.44%)477.9 V3.45 V (0.72%)1357.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.79 V (0.37%)478.2 V2.96 V (0.62%)1164.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.57 V (0.33%)478.4 V2.59 V (0.54%)1018.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.25 V (0.26%)478.7 V2.07 V (0.43%)814.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.05 V (0.22%)479.0 V1.72 V (0.36%)678.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.84 V (0.17%)479.2 V1.38 V (0.29%)543.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.63 V (0.13%)479.4 V1.03 V (0.22%)407.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 75 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 75 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 1.25V (0.26%) and delivers 478.7V at the load.

What size aluminum wire is required for 375 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 1.38V (0.29%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.