🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 13.94V (2.9%)
Voltage at Load End466.6 VLoss: 13.44 V (931.3 W)
Power & Breaker (125%)33.26 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A217.26 V (45.26%)262.7 V358.38 V (74.66%)15052.4 WDrop/Amp High
12 AWG3.31 mm²20 A136.53 V (28.44%)343.5 V225.21 V (46.92%)9458.9 WDrop/Amp High
10 AWG5.26 mm²30 A85.91 V (17.9%)394.1 V141.72 V (29.52%)5952.3 WDrop/Amp High
8 AWG8.37 mm²50 A53.99 V (11.25%)426.0 V89.06 V (18.55%)3740.6 WDrop/Amp High
6 AWG13.3 mm²65 A33.98 V (7.08%)446.0 V56.05 V (11.68%)2354.1 WDrop/Amp High
4 AWG21.15 mm²85 A21.37 V (4.45%)458.6 V35.25 V (7.34%)1480.3 W~ ≤5%
3 AWG26.67 mm²100 A16.94 V (3.53%)463.1 V27.95 V (5.82%)1173.9 W~ ≤5%
2 AWG33.62 mm²115 A13.44 V (2.8%)466.6 V22.17 V (4.62%)931.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A10.66 V (2.22%)469.3 V17.58 V (3.66%)738.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A8.45 V (1.76%)471.6 V13.94 V (2.9%)585.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A6.7 V (1.4%)473.3 V11.05 V (2.3%)464.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.32 V (1.11%)474.7 V8.77 V (1.83%)368.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.22 V (0.88%)475.8 V6.95 V (1.45%)292.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.57 V (0.74%)476.4 V5.88 V (1.23%)247.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.97 V (0.62%)477.0 V4.9 V (1.02%)206.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.55 V (0.53%)477.5 V4.2 V (0.88%)176.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.23 V (0.46%)477.8 V3.68 V (0.77%)154.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.78 V (0.37%)478.2 V2.94 V (0.61%)123.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.49 V (0.31%)478.5 V2.45 V (0.51%)103.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.19 V (0.25%)478.8 V1.96 V (0.41%)82.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.89 V (0.19%)479.1 V1.47 V (0.31%)61.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 1000 feet one-way at 480V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 13.44V (2.8%) and delivers 466.6V at the load.

What size aluminum wire is required for 40 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 13.94V (2.9%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.