🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 13.91V (2.9%)
Voltage at Load End466.6 VLoss: 13.4 V (1857.3 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A434.53 V (90.53%)45.5 V716.77 V (149.33%)60209.7 WDrop/Amp High
12 AWG3.31 mm²20 A273.06 V (56.89%)206.9 V450.41 V (93.84%)37835.7 WDrop/Amp High
10 AWG5.26 mm²30 A171.83 V (35.8%)308.2 V283.44 V (59.05%)23809.2 WDrop/Amp High
8 AWG8.37 mm²50 A107.98 V (22.5%)372.0 V178.12 V (37.11%)14962.5 WDrop/Amp High
6 AWG13.3 mm²65 A67.96 V (14.16%)412.0 V112.1 V (23.35%)9416.3 WDrop/Amp High
4 AWG21.15 mm²85 A42.73 V (8.9%)437.3 V70.49 V (14.69%)5921.3 WDrop/Amp High
3 AWG26.67 mm²100 A33.89 V (7.06%)446.1 V55.9 V (11.65%)4695.8 WDrop/Amp High
2 AWG33.62 mm²115 A26.88 V (5.6%)453.1 V44.34 V (9.24%)3725.1 WDrop/Amp High
1 AWG42.41 mm²130 A21.31 V (4.44%)458.7 V35.15 V (7.32%)2953.0 W~ ≤5%
1/0 AWG53.49 mm²150 A16.9 V (3.52%)463.1 V27.87 V (5.81%)2341.3 W~ ≤5%
2/0 AWG67.43 mm²175 A13.4 V (2.79%)466.6 V22.11 V (4.61%)1857.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A10.63 V (2.21%)469.4 V17.54 V (3.65%)1473.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A8.43 V (1.76%)471.6 V13.91 V (2.9%)1168.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A7.13 V (1.49%)472.9 V11.77 V (2.45%)988.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.95 V (1.24%)474.1 V9.81 V (2.04%)823.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.1 V (1.06%)474.9 V8.41 V (1.75%)706.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.46 V (0.93%)475.5 V7.36 V (1.53%)617.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.57 V (0.74%)476.4 V5.88 V (1.23%)494.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.97 V (0.62%)477.0 V4.9 V (1.02%)412.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.38 V (0.5%)477.6 V3.92 V (0.82%)329.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.78 V (0.37%)478.2 V2.94 V (0.61%)247.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 1000 feet one-way at 480V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 13.4V (2.79%) and delivers 466.6V at the load.

What size aluminum wire is required for 80 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 13.91V (2.9%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.