🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 0.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.04V (0.85%)
Voltage at Load End237.9 VLoss: 2.06 V (823.9 W)
Power & Breaker (125%)96.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.05 V (125.44%)0.0 V496.59 V (206.91%)120419.4 WDrop/Amp High
12 AWG3.31 mm²20 A189.18 V (78.82%)50.8 V312.06 V (130.02%)75671.4 WDrop/Amp High
10 AWG5.26 mm²30 A119.05 V (49.6%)121.0 V196.37 V (81.82%)47618.3 WDrop/Amp High
8 AWG8.37 mm²50 A74.81 V (31.17%)165.2 V123.41 V (51.42%)29925.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.08 V (19.62%)192.9 V77.66 V (32.36%)18832.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.61 V (12.34%)210.4 V48.84 V (20.35%)11842.7 WDrop/Amp High
3 AWG26.67 mm²100 A23.48 V (9.78%)216.5 V38.73 V (16.14%)9391.5 WDrop/Amp High
2 AWG33.62 mm²115 A18.63 V (7.76%)221.4 V30.72 V (12.8%)7450.1 WDrop/Amp High
1 AWG42.41 mm²130 A14.76 V (6.15%)225.2 V24.36 V (10.15%)5906.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.71 V (4.88%)228.3 V19.31 V (8.05%)4682.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.29 V (3.87%)230.7 V15.32 V (6.38%)3714.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.37 V (3.07%)232.6 V12.15 V (5.06%)2946.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.84 V (2.43%)234.2 V9.64 V (4.01%)2336.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.94 V (2.06%)235.1 V8.15 V (3.4%)1976.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.12 V (1.72%)235.9 V6.8 V (2.83%)1647.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.53 V (1.47%)236.5 V5.83 V (2.43%)1412.7 WDrop/Amp High
400 kcmil202.7 mm²335 A3.09 V (1.29%)236.9 V5.1 V (2.12%)1235.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.47 V (1.03%)237.5 V4.08 V (1.7%)988.4 WDrop/Amp High
600 kcmil304.0 mm²420 A2.06 V (0.86%)237.9 V3.4 V (1.42%)823.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.65 V (0.69%)238.4 V2.72 V (1.13%)659.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.24 V (0.51%)238.8 V2.04 V (0.85%)494.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 120 feet one-way at 240V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 2.06V (0.86%) and delivers 237.9V at the load.

What size aluminum wire is required for 400 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.04V (0.85%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.