⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)2 AWGDrop: 6.14V (2.56%)
Voltage at Load End234.1 VLoss: 5.92 V (473.7 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A60.21 V (25.09%)179.8 V99.32 V (41.38%)4816.8 WDrop/Amp High
12 AWG3.31 mm²20 A37.84 V (15.76%)202.2 V62.41 V (26.0%)3026.9 WDrop/Amp High
10 AWG5.26 mm²30 A23.81 V (9.92%)216.2 V39.27 V (16.36%)1904.7 WDrop/Amp High
8 AWG8.37 mm²50 A14.96 V (6.23%)225.0 V24.68 V (10.28%)1197.0 WDrop/Amp High
6 AWG13.3 mm²65 A9.42 V (3.92%)230.6 V15.53 V (6.47%)753.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.92 V (2.47%)234.1 V9.77 V (4.07%)473.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.7 V (1.96%)235.3 V7.75 V (3.23%)375.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.73 V (1.55%)236.3 V6.14 V (2.56%)298.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.95 V (1.23%)237.0 V4.87 V (2.03%)236.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.34 V (0.98%)237.7 V3.86 V (1.61%)187.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.86 V (0.77%)238.1 V3.06 V (1.28%)148.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.47 V (0.61%)238.5 V2.43 V (1.01%)117.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.17 V (0.49%)238.8 V1.93 V (0.8%)93.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.99 V (0.41%)239.0 V1.63 V (0.68%)79.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.82 V (0.34%)239.2 V1.36 V (0.57%)65.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.71 V (0.29%)239.3 V1.17 V (0.49%)56.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.62 V (0.26%)239.4 V1.02 V (0.42%)49.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.49 V (0.21%)239.5 V0.82 V (0.34%)39.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.41 V (0.17%)239.6 V0.68 V (0.28%)33.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.14%)239.7 V0.54 V (0.23%)26.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.1%)239.8 V0.41 V (0.17%)19.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 120 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.92V (2.47%) and delivers 234.1V at the load.

What size aluminum wire is required for 80 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 6.14V (2.56%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.