⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 20 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.45%
Aluminum Wire (≤3% Drop)8 AWGDrop: 1.78V (0.74%)
Voltage at Load End238.9 VLoss: 1.08 V (74.8 W)
Power & Breaker (125%)16.63 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.35 V (1.81%)235.7 V7.17 V (2.99%)301.0 WDrop/Amp High
12 AWG3.31 mm²20 A2.73 V (1.14%)237.3 V4.5 V (1.88%)189.2 WDrop/Amp High
10 AWG5.26 mm²30 A1.72 V (0.72%)238.3 V2.83 V (1.18%)119.0 WDrop/Amp High
8 AWG8.37 mm²50 A1.08 V (0.45%)238.9 V1.78 V (0.74%)74.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.68 V (0.28%)239.3 V1.12 V (0.47%)47.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.43 V (0.18%)239.6 V0.7 V (0.29%)29.6 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.34 V (0.14%)239.7 V0.56 V (0.23%)23.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.27 V (0.11%)239.7 V0.44 V (0.18%)18.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.21 V (0.09%)239.8 V0.35 V (0.15%)14.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.17 V (0.07%)239.8 V0.28 V (0.12%)11.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.13 V (0.06%)239.9 V0.22 V (0.09%)9.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.11 V (0.04%)239.9 V0.18 V (0.07%)7.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.08 V (0.04%)239.9 V0.14 V (0.06%)5.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.07 V (0.03%)239.9 V0.12 V (0.05%)4.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.06 V (0.02%)239.9 V0.1 V (0.04%)4.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.05 V (0.02%)239.9 V0.08 V (0.04%)3.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.04 V (0.02%)240.0 V0.07 V (0.03%)3.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.01%)240.0 V0.06 V (0.02%)2.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.01%)240.0 V0.05 V (0.02%)2.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.01%)240.0 V0.04 V (0.02%)1.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.01%)240.0 V0.03 V (0.01%)1.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 20 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 1.08V (0.45%) and delivers 238.9V at the load.

What size aluminum wire is required for 40 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 1.78V (0.74%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.