🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.12%
Aluminum Wire (≤3% Drop)8 AWGDrop: 4.45V (1.86%)
Voltage at Load End237.3 VLoss: 2.7 V (187.0 W)
Power & Breaker (125%)16.63 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.86 V (4.53%)229.1 V17.92 V (7.47%)752.6 WDrop/Amp High
12 AWG3.31 mm²20 A6.83 V (2.84%)233.2 V11.26 V (4.69%)472.9 WDrop/Amp High
10 AWG5.26 mm²30 A4.3 V (1.79%)235.7 V7.09 V (2.95%)297.6 WDrop/Amp High
8 AWG8.37 mm²50 A2.7 V (1.12%)237.3 V4.45 V (1.86%)187.0 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.7 V (0.71%)238.3 V2.8 V (1.17%)117.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.07 V (0.45%)238.9 V1.76 V (0.73%)74.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.85 V (0.35%)239.2 V1.4 V (0.58%)58.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.67 V (0.28%)239.3 V1.11 V (0.46%)46.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.53 V (0.22%)239.5 V0.88 V (0.37%)36.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.42 V (0.18%)239.6 V0.7 V (0.29%)29.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.34 V (0.14%)239.7 V0.55 V (0.23%)23.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.27 V (0.11%)239.7 V0.44 V (0.18%)18.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.21 V (0.09%)239.8 V0.35 V (0.14%)14.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.18 V (0.07%)239.8 V0.29 V (0.12%)12.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.15 V (0.06%)239.9 V0.25 V (0.1%)10.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.05%)239.9 V0.21 V (0.09%)8.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.11 V (0.05%)239.9 V0.18 V (0.08%)7.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.04%)239.9 V0.15 V (0.06%)6.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.03%)239.9 V0.12 V (0.05%)5.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.02%)239.9 V0.1 V (0.04%)4.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.02%)240.0 V0.07 V (0.03%)3.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 50 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.7V (1.12%) and delivers 237.3V at the load.

What size aluminum wire is required for 40 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 4.45V (1.86%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.