⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.8%
Aluminum Wire (≤3% Drop)8 AWGDrop: 7.12V (2.97%)
Voltage at Load End235.7 VLoss: 4.32 V (299.3 W)
Power & Breaker (125%)16.63 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A17.38 V (7.24%)222.6 V28.67 V (11.95%)1204.2 WDrop/Amp High
12 AWG3.31 mm²20 A10.92 V (4.55%)229.1 V18.02 V (7.51%)756.7 WDrop/Amp High
10 AWG5.26 mm²30 A6.87 V (2.86%)233.1 V11.34 V (4.72%)476.2 WDrop/Amp High
8 AWG8.37 mm²50 A4.32 V (1.8%)235.7 V7.12 V (2.97%)299.3 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A2.72 V (1.13%)237.3 V4.48 V (1.87%)188.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.71 V (0.71%)238.3 V2.82 V (1.17%)118.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.36 V (0.56%)238.6 V2.24 V (0.93%)93.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.08 V (0.45%)238.9 V1.77 V (0.74%)74.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.85 V (0.36%)239.1 V1.41 V (0.59%)59.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.68 V (0.28%)239.3 V1.11 V (0.46%)46.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.54 V (0.22%)239.5 V0.88 V (0.37%)37.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.43 V (0.18%)239.6 V0.7 V (0.29%)29.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.34 V (0.14%)239.7 V0.56 V (0.23%)23.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.29 V (0.12%)239.7 V0.47 V (0.2%)19.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.24 V (0.1%)239.8 V0.39 V (0.16%)16.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.2 V (0.08%)239.8 V0.34 V (0.14%)14.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.18 V (0.07%)239.8 V0.29 V (0.12%)12.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.14 V (0.06%)239.9 V0.24 V (0.1%)9.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.12 V (0.05%)239.9 V0.2 V (0.08%)8.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.1 V (0.04%)239.9 V0.16 V (0.07%)6.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.07 V (0.03%)239.9 V0.12 V (0.05%)4.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 80 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.32V (1.8%) and delivers 235.7V at the load.

What size aluminum wire is required for 40 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 7.12V (2.97%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.