🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 0.32%
Aluminum Wire (≤3% Drop)4 AWGDrop: 1.59V (0.33%)
Voltage at Load End478.5 VLoss: 1.53 V (158.9 W)
Power & Breaker (125%)49.88 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A9.78 V (2.04%)470.2 V16.13 V (3.36%)1016.0 WDrop/Amp High
12 AWG3.31 mm²20 A6.14 V (1.28%)473.9 V10.13 V (2.11%)638.5 WDrop/Amp High
10 AWG5.26 mm²30 A3.87 V (0.81%)476.1 V6.38 V (1.33%)401.8 WDrop/Amp High
8 AWG8.37 mm²50 A2.43 V (0.51%)477.6 V4.01 V (0.83%)252.5 WDrop/Amp High
6 AWG13.3 mm²65 A1.53 V (0.32%)478.5 V2.52 V (0.53%)158.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.96 V (0.2%)479.0 V1.59 V (0.33%)99.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.76 V (0.16%)479.2 V1.26 V (0.26%)79.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.6 V (0.13%)479.4 V1.0 V (0.21%)62.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.48 V (0.1%)479.5 V0.79 V (0.16%)49.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.38 V (0.08%)479.6 V0.63 V (0.13%)39.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.3 V (0.06%)479.7 V0.5 V (0.1%)31.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.24 V (0.05%)479.8 V0.39 V (0.08%)24.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.19 V (0.04%)479.8 V0.31 V (0.07%)19.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.16 V (0.03%)479.8 V0.26 V (0.06%)16.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.13 V (0.03%)479.9 V0.22 V (0.05%)13.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.11 V (0.02%)479.9 V0.19 V (0.04%)11.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.02%)479.9 V0.17 V (0.03%)10.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.02%)479.9 V0.13 V (0.03%)8.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.01%)479.9 V0.11 V (0.02%)7.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.01%)479.9 V0.09 V (0.02%)5.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.01%)480.0 V0.07 V (0.01%)4.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 30 feet one-way at 480V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 1.53V (0.32%) and delivers 478.5V at the load.

What size aluminum wire is required for 60 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 1.59V (0.33%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.