⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

40 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 40 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.43%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.4V (2.83%)
Voltage at Load End117.1 VLoss: 2.92 V (116.8 W)
Power & Breaker (125%)4.8 kW50A Breaker Recommended

All AWG & kcmil Wire Gauges for 40 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A150.52 V (125.44%)0.0 V248.29 V (206.91%)6021.0 WDrop/Amp High
12 AWG3.31 mm²20 A94.59 V (78.82%)25.4 V156.03 V (130.02%)3783.6 WDrop/Amp High
10 AWG5.26 mm²30 A59.52 V (49.6%)60.5 V98.19 V (81.82%)2380.9 WDrop/Amp High
8 AWG8.37 mm²50 A37.41 V (31.17%)82.6 V61.7 V (51.42%)1496.3 WDrop/Amp High
6 AWG13.3 mm²65 A23.54 V (19.62%)96.5 V38.83 V (32.36%)941.6 WDrop/Amp High
4 AWG21.15 mm²85 A14.8 V (12.34%)105.2 V24.42 V (20.35%)592.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.74 V (9.78%)108.3 V19.36 V (16.14%)469.6 WDrop/Amp High
2 AWG33.62 mm²115 A9.31 V (7.76%)110.7 V15.36 V (12.8%)372.5 WDrop/Amp High
1 AWG42.41 mm²130 A7.38 V (6.15%)112.6 V12.18 V (10.15%)295.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.85 V (4.88%)114.1 V9.66 V (8.05%)234.1 W~ ≤5%
2/0 AWG67.43 mm²175 A4.64 V (3.87%)115.4 V7.66 V (6.38%)185.7 W~ ≤5%
3/0 AWG85.01 mm²200 A3.68 V (3.07%)116.3 V6.08 V (5.06%)147.3 W~ ≤5%
4/0 AWG107.2 mm²230 A2.92 V (2.43%)117.1 V4.82 V (4.01%)116.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.47 V (2.06%)117.5 V4.08 V (3.4%)98.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.06 V (1.72%)117.9 V3.4 V (2.83%)82.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.77 V (1.47%)118.2 V2.91 V (2.43%)70.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.54 V (1.29%)118.5 V2.55 V (2.12%)61.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.24 V (1.03%)118.8 V2.04 V (1.7%)49.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.03 V (0.86%)119.0 V1.7 V (1.42%)41.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.82 V (0.69%)119.2 V1.36 V (1.13%)33.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.62 V (0.51%)119.4 V1.02 V (0.85%)24.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 40 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 40A load over 600 feet one-way at 120V (1-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 2.92V (2.43%) and delivers 117.1V at the load.

What size aluminum wire is required for 40 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.4V (2.83%).

What breaker size is needed for a 40A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (40A × 1.25 = 50.0A), which corresponds to a standard 50A circuit breaker.