⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 0.29%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.68V (0.28%)
Voltage at Load End239.3 VLoss: 0.69 V (274.6 W)
Power & Breaker (125%)96.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A100.35 V (41.81%)139.7 V165.53 V (68.97%)40139.8 WDrop/Amp High
12 AWG3.31 mm²20 A63.06 V (26.27%)176.9 V104.02 V (43.34%)25223.8 WDrop/Amp High
10 AWG5.26 mm²30 A39.68 V (16.53%)200.3 V65.46 V (27.27%)15872.8 WDrop/Amp High
8 AWG8.37 mm²50 A24.94 V (10.39%)215.1 V41.14 V (17.14%)9975.0 WDrop/Amp High
6 AWG13.3 mm²65 A15.69 V (6.54%)224.3 V25.89 V (10.79%)6277.5 WDrop/Amp High
4 AWG21.15 mm²85 A9.87 V (4.11%)230.1 V16.28 V (6.78%)3947.6 WDrop/Amp High
3 AWG26.67 mm²100 A7.83 V (3.26%)232.2 V12.91 V (5.38%)3130.5 WDrop/Amp High
2 AWG33.62 mm²115 A6.21 V (2.59%)233.8 V10.24 V (4.27%)2483.4 WDrop/Amp High
1 AWG42.41 mm²130 A4.92 V (2.05%)235.1 V8.12 V (3.38%)1968.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.9 V (1.63%)236.1 V6.44 V (2.68%)1560.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.1 V (1.29%)236.9 V5.11 V (2.13%)1238.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.46 V (1.02%)237.5 V4.05 V (1.69%)982.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.95 V (0.81%)238.1 V3.21 V (1.34%)778.8 WDrop/Amp High
250 kcmil126.7 mm²255 A1.65 V (0.69%)238.4 V2.72 V (1.13%)659.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.37 V (0.57%)238.6 V2.27 V (0.94%)549.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.18 V (0.49%)238.8 V1.94 V (0.81%)470.9 WDrop/Amp High
400 kcmil202.7 mm²335 A1.03 V (0.43%)239.0 V1.7 V (0.71%)411.9 WDrop/Amp High
500 kcmil253.4 mm²380 A0.82 V (0.34%)239.2 V1.36 V (0.57%)329.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.69 V (0.29%)239.3 V1.13 V (0.47%)274.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.55 V (0.23%)239.5 V0.91 V (0.38%)219.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.41 V (0.17%)239.6 V0.68 V (0.28%)164.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 40 feet one-way at 240V (1-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 0.69V (0.29%) and delivers 239.3V at the load.

What size aluminum wire is required for 400 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.68V (0.28%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.