⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 150 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.34V (0.49%)
Voltage at Load End478.1 VLoss: 1.9 V (1395.2 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 150 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A346.26 V (72.14%)133.7 V571.17 V (118.99%)254891.7 WDrop/Amp High
12 AWG3.31 mm²20 A217.59 V (45.33%)262.4 V358.92 V (74.78%)160173.7 WDrop/Amp High
10 AWG5.26 mm²30 A136.93 V (28.53%)343.1 V225.86 V (47.05%)100793.7 WDrop/Amp High
8 AWG8.37 mm²50 A86.05 V (17.93%)394.0 V141.94 V (29.57%)63342.3 WDrop/Amp High
6 AWG13.3 mm²65 A54.15 V (11.28%)425.8 V89.33 V (18.61%)39862.8 WDrop/Amp High
4 AWG21.15 mm²85 A34.05 V (7.09%)445.9 V56.17 V (11.7%)25067.4 WDrop/Amp High
3 AWG26.67 mm²100 A27.01 V (5.63%)453.0 V44.55 V (9.28%)19879.1 WDrop/Amp High
2 AWG33.62 mm²115 A21.42 V (4.46%)458.6 V35.34 V (7.36%)15769.6 WDrop/Amp High
1 AWG42.41 mm²130 A16.98 V (3.54%)463.0 V28.01 V (5.84%)12501.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.46 V (2.81%)466.5 V22.21 V (4.63%)9911.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.68 V (2.23%)469.3 V17.62 V (3.67%)7862.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.47 V (1.77%)471.5 V13.98 V (2.91%)6236.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.72 V (1.4%)473.3 V11.08 V (2.31%)4945.7 WDrop/Amp High
250 kcmil126.7 mm²255 A5.68 V (1.18%)474.3 V9.38 V (1.95%)4184.5 WDrop/Amp High
300 kcmil152.0 mm²285 A4.74 V (0.99%)475.3 V7.82 V (1.63%)3488.0 WDrop/Amp High
350 kcmil177.3 mm²310 A4.06 V (0.85%)475.9 V6.7 V (1.4%)2990.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.55 V (0.74%)476.4 V5.86 V (1.22%)2615.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.84 V (0.59%)477.2 V4.69 V (0.98%)2092.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.37 V (0.49%)477.6 V3.91 V (0.81%)1744.0 WDrop/Amp High
750 kcmil380.0 mm²475 A1.9 V (0.39%)478.1 V3.13 V (0.65%)1395.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.42 V (0.3%)478.6 V2.34 V (0.49%)1046.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 150 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 150 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.9V (0.39%) and delivers 478.1V at the load.

What size aluminum wire is required for 425 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.34V (0.49%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.