🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.33%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.95V (0.41%)
Voltage at Load End478.4 VLoss: 1.58 V (1162.7 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A288.55 V (60.12%)191.4 V475.98 V (99.16%)212409.8 WDrop/Amp High
12 AWG3.31 mm²20 A181.33 V (37.78%)298.7 V299.1 V (62.31%)133478.1 WDrop/Amp High
10 AWG5.26 mm²30 A114.1 V (23.77%)365.9 V188.22 V (39.21%)83994.7 WDrop/Amp High
8 AWG8.37 mm²50 A71.71 V (14.94%)408.3 V118.28 V (24.64%)52785.2 WDrop/Amp High
6 AWG13.3 mm²65 A45.13 V (9.4%)434.9 V74.44 V (15.51%)33219.0 WDrop/Amp High
4 AWG21.15 mm²85 A28.38 V (5.91%)451.6 V46.81 V (9.75%)20889.5 WDrop/Amp High
3 AWG26.67 mm²100 A22.5 V (4.69%)457.5 V37.12 V (7.73%)16565.9 WDrop/Amp High
2 AWG33.62 mm²115 A17.85 V (3.72%)462.1 V29.45 V (6.13%)13141.4 WDrop/Amp High
1 AWG42.41 mm²130 A14.15 V (2.95%)465.8 V23.34 V (4.86%)10417.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.22 V (2.34%)468.8 V18.51 V (3.86%)8259.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.9 V (1.85%)471.1 V14.68 V (3.06%)6552.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.06 V (1.47%)472.9 V11.65 V (2.43%)5197.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.6 V (1.17%)474.4 V9.24 V (1.92%)4121.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.74 V (0.99%)475.3 V7.81 V (1.63%)3487.1 WDrop/Amp High
300 kcmil152.0 mm²285 A3.95 V (0.82%)476.1 V6.51 V (1.36%)2906.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.39 V (0.71%)476.6 V5.58 V (1.16%)2491.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.96 V (0.62%)477.0 V4.88 V (1.02%)2179.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.37 V (0.49%)477.6 V3.91 V (0.81%)1743.5 WDrop/Amp High
600 kcmil304.0 mm²420 A1.97 V (0.41%)478.0 V3.26 V (0.68%)1453.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.58 V (0.33%)478.4 V2.61 V (0.54%)1162.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.18 V (0.25%)478.8 V1.95 V (0.41%)871.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 125 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.58V (0.33%) and delivers 478.4V at the load.

What size aluminum wire is required for 425 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.95V (0.41%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.