⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.26%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.56V (0.33%)
Voltage at Load End478.7 VLoss: 1.26 V (930.1 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A230.84 V (48.09%)249.2 V380.78 V (79.33%)169927.8 WDrop/Amp High
12 AWG3.31 mm²20 A145.06 V (30.22%)334.9 V239.28 V (49.85%)106782.4 WDrop/Amp High
10 AWG5.26 mm²30 A91.28 V (19.02%)388.7 V150.58 V (31.37%)67195.8 WDrop/Amp High
8 AWG8.37 mm²50 A57.37 V (11.95%)422.6 V94.63 V (19.71%)42228.2 WDrop/Amp High
6 AWG13.3 mm²65 A36.1 V (7.52%)443.9 V59.55 V (12.41%)26575.2 WDrop/Amp High
4 AWG21.15 mm²85 A22.7 V (4.73%)457.3 V37.45 V (7.8%)16711.6 WDrop/Amp High
3 AWG26.67 mm²100 A18.0 V (3.75%)462.0 V29.7 V (6.19%)13252.7 WDrop/Amp High
2 AWG33.62 mm²115 A14.28 V (2.98%)465.7 V23.56 V (4.91%)10513.1 WDrop/Amp High
1 AWG42.41 mm²130 A11.32 V (2.36%)468.7 V18.68 V (3.89%)8334.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.98 V (1.87%)471.0 V14.81 V (3.08%)6607.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.12 V (1.48%)472.9 V11.75 V (2.45%)5241.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.65 V (1.18%)474.4 V9.32 V (1.94%)4157.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.48 V (0.93%)475.5 V7.39 V (1.54%)3297.1 WDrop/Amp High
250 kcmil126.7 mm²255 A3.79 V (0.79%)476.2 V6.25 V (1.3%)2789.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.16 V (0.66%)476.8 V5.21 V (1.09%)2325.3 WDrop/Amp High
350 kcmil177.3 mm²310 A2.71 V (0.56%)477.3 V4.47 V (0.93%)1993.5 WDrop/Amp High
400 kcmil202.7 mm²335 A2.37 V (0.49%)477.6 V3.91 V (0.81%)1743.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.89 V (0.39%)478.1 V3.13 V (0.65%)1394.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.58 V (0.33%)478.4 V2.61 V (0.54%)1162.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.26 V (0.26%)478.7 V2.08 V (0.43%)930.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.95 V (0.2%)479.1 V1.56 V (0.33%)697.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 100 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.26V (0.26%) and delivers 478.7V at the load.

What size aluminum wire is required for 425 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.56V (0.33%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.