425 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.88V (0.39%)
Voltage at Load End478.5 VLoss: 1.52 V (1116.2 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A277.01 V (57.71%)203.0 V456.94 V (95.2%)203913.4 WDrop/Amp High
12 AWG3.31 mm²20 A174.07 V (36.27%)305.9 V287.14 V (59.82%)128138.9 WDrop/Amp High
10 AWG5.26 mm²30 A109.54 V (22.82%)370.5 V180.69 V (37.64%)80635.0 WDrop/Amp High
8 AWG8.37 mm²50 A68.84 V (14.34%)411.2 V113.55 V (23.66%)50673.8 WDrop/Amp High
6 AWG13.3 mm²65 A43.32 V (9.03%)436.7 V71.46 V (14.89%)31890.2 WDrop/Amp High
4 AWG21.15 mm²85 A27.24 V (5.68%)452.8 V44.94 V (9.36%)20053.9 WDrop/Amp High
3 AWG26.67 mm²100 A21.6 V (4.5%)458.4 V35.64 V (7.42%)15903.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.14 V (3.57%)462.9 V28.27 V (5.89%)12615.7 WDrop/Amp High
1 AWG42.41 mm²130 A13.59 V (2.83%)466.4 V22.41 V (4.67%)10000.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.77 V (2.24%)469.2 V17.77 V (3.7%)7929.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.54 V (1.78%)471.5 V14.1 V (2.94%)6290.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.78 V (1.41%)473.2 V11.18 V (2.33%)4989.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.37 V (1.12%)474.6 V8.87 V (1.85%)3956.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.55 V (0.95%)475.5 V7.5 V (1.56%)3347.6 WDrop/Amp High
300 kcmil152.0 mm²285 A3.79 V (0.79%)476.2 V6.25 V (1.3%)2790.4 WDrop/Amp High
350 kcmil177.3 mm²310 A3.25 V (0.68%)476.8 V5.36 V (1.12%)2392.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.84 V (0.59%)477.2 V4.69 V (0.98%)2092.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.27 V (0.47%)477.7 V3.75 V (0.78%)1673.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.9 V (0.39%)478.1 V3.13 V (0.65%)1395.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.52 V (0.32%)478.5 V2.5 V (0.52%)1116.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.14 V (0.24%)478.9 V1.88 V (0.39%)837.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 120 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.52V (0.32%) and delivers 478.5V at the load.

What size aluminum wire is required for 425 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.88V (0.39%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.