🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.16%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.94V (0.2%)
Voltage at Load End479.2 VLoss: 0.76 V (558.1 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A138.51 V (28.86%)341.5 V228.47 V (47.6%)101956.7 WDrop/Amp High
12 AWG3.31 mm²20 A87.04 V (18.13%)393.0 V143.57 V (29.91%)64069.5 WDrop/Amp High
10 AWG5.26 mm²30 A54.77 V (11.41%)425.2 V90.35 V (18.82%)40317.5 WDrop/Amp High
8 AWG8.37 mm²50 A34.42 V (7.17%)445.6 V56.78 V (11.83%)25336.9 WDrop/Amp High
6 AWG13.3 mm²65 A21.66 V (4.51%)458.3 V35.73 V (7.44%)15945.1 WDrop/Amp High
4 AWG21.15 mm²85 A13.62 V (2.84%)466.4 V22.47 V (4.68%)10026.9 WDrop/Amp High
3 AWG26.67 mm²100 A10.8 V (2.25%)469.2 V17.82 V (3.71%)7951.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.57 V (1.79%)471.4 V14.13 V (2.94%)6307.9 WDrop/Amp High
1 AWG42.41 mm²130 A6.79 V (1.42%)473.2 V11.21 V (2.33%)5000.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.39 V (1.12%)474.6 V8.88 V (1.85%)3964.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.27 V (0.89%)475.7 V7.05 V (1.47%)3145.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.39 V (0.71%)476.6 V5.59 V (1.16%)2494.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.69 V (0.56%)477.3 V4.43 V (0.92%)1978.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.27 V (0.47%)477.7 V3.75 V (0.78%)1673.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.9 V (0.39%)478.1 V3.13 V (0.65%)1395.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.62 V (0.34%)478.4 V2.68 V (0.56%)1196.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.42 V (0.3%)478.6 V2.34 V (0.49%)1046.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.14 V (0.24%)478.9 V1.88 V (0.39%)836.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.95 V (0.2%)479.1 V1.56 V (0.33%)697.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.76 V (0.16%)479.2 V1.25 V (0.26%)558.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.57 V (0.12%)479.4 V0.94 V (0.2%)418.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 60 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.76V (0.16%) and delivers 479.2V at the load.

What size aluminum wire is required for 425 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.94V (0.2%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.