⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.6%
Aluminum Wire (≤3% Drop)2 AWGDrop: 5.61V (2.7%)
Voltage at Load End202.6 VLoss: 5.41 V (421.5 W)
Power & Breaker (125%)16.21 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.99 V (26.44%)153.0 V90.72 V (43.61%)4286.4 WDrop/Amp High
12 AWG3.31 mm²20 A34.56 V (16.61%)173.4 V57.01 V (27.41%)2693.6 WDrop/Amp High
10 AWG5.26 mm²30 A21.75 V (10.46%)186.3 V35.87 V (17.25%)1695.0 WDrop/Amp High
8 AWG8.37 mm²50 A13.67 V (6.57%)194.3 V22.54 V (10.84%)1065.2 WDrop/Amp High
6 AWG13.3 mm²65 A8.6 V (4.13%)199.4 V14.19 V (6.82%)670.4 W~ ≤5%
4 AWG21.15 mm²85 A5.41 V (2.6%)202.6 V8.92 V (4.29%)421.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.29 V (2.06%)203.7 V7.07 V (3.4%)334.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.4 V (1.64%)204.6 V5.61 V (2.7%)265.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.7 V (1.3%)205.3 V4.45 V (2.14%)210.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.14 V (1.03%)205.9 V3.53 V (1.7%)166.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.7 V (0.82%)206.3 V2.8 V (1.35%)132.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.35 V (0.65%)206.7 V2.22 V (1.07%)104.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.07 V (0.51%)206.9 V1.76 V (0.85%)83.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.9 V (0.43%)207.1 V1.49 V (0.72%)70.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.75 V (0.36%)207.2 V1.24 V (0.6%)58.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.65 V (0.31%)207.4 V1.06 V (0.51%)50.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.56 V (0.27%)207.4 V0.93 V (0.45%)44.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.45 V (0.22%)207.5 V0.74 V (0.36%)35.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.38 V (0.18%)207.6 V0.62 V (0.3%)29.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.3 V (0.14%)207.7 V0.5 V (0.24%)23.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.11%)207.8 V0.37 V (0.18%)17.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 225 feet one-way at 208V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.41V (2.6%) and delivers 202.6V at the load.

What size aluminum wire is required for 45 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 5.61V (2.7%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.