🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)3 AWGDrop: 7.07V (2.95%)
Voltage at Load End234.6 VLoss: 5.41 V (421.5 W)
Power & Breaker (125%)18.71 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.99 V (22.91%)185.0 V90.72 V (37.8%)4286.4 WDrop/Amp High
12 AWG3.31 mm²20 A34.56 V (14.4%)205.4 V57.01 V (23.75%)2693.6 WDrop/Amp High
10 AWG5.26 mm²30 A21.75 V (9.06%)218.3 V35.87 V (14.95%)1695.0 WDrop/Amp High
8 AWG8.37 mm²50 A13.67 V (5.69%)226.3 V22.54 V (9.39%)1065.2 WDrop/Amp High
6 AWG13.3 mm²65 A8.6 V (3.58%)231.4 V14.19 V (5.91%)670.4 W~ ≤5%
4 AWG21.15 mm²85 A5.41 V (2.25%)234.6 V8.92 V (3.72%)421.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.29 V (1.79%)235.7 V7.07 V (2.95%)334.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.4 V (1.42%)236.6 V5.61 V (2.34%)265.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.7 V (1.12%)237.3 V4.45 V (1.85%)210.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.14 V (0.89%)237.9 V3.53 V (1.47%)166.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.7 V (0.71%)238.3 V2.8 V (1.17%)132.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.35 V (0.56%)238.7 V2.22 V (0.92%)104.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.07 V (0.44%)238.9 V1.76 V (0.73%)83.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.9 V (0.38%)239.1 V1.49 V (0.62%)70.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.75 V (0.31%)239.2 V1.24 V (0.52%)58.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.65 V (0.27%)239.4 V1.06 V (0.44%)50.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.56 V (0.24%)239.4 V0.93 V (0.39%)44.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.45 V (0.19%)239.5 V0.74 V (0.31%)35.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.38 V (0.16%)239.6 V0.62 V (0.26%)29.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.3 V (0.13%)239.7 V0.5 V (0.21%)23.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.09%)239.8 V0.37 V (0.16%)17.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 225 feet one-way at 240V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.41V (2.25%) and delivers 234.6V at the load.

What size aluminum wire is required for 45 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 7.07V (2.95%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.