🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 350 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.67V (5.57%)
Voltage at Load End11.8 VLoss: 0.2 V (9.1 W)
Power & Breaker (125%)0.54 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 350 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A98.78 V (823.18%)0.0 V162.94 V (1357.86%)4445.2 WDrop/Amp High
12 AWG3.31 mm²20 A62.07 V (517.29%)0.0 V102.39 V (853.28%)2793.3 WDrop/Amp High
10 AWG5.26 mm²30 A39.06 V (325.52%)0.0 V64.43 V (536.95%)1757.8 WDrop/Amp High
8 AWG8.37 mm²50 A24.55 V (204.57%)0.0 V40.49 V (337.44%)1104.7 WDrop/Amp High
6 AWG13.3 mm²65 A15.45 V (128.74%)0.0 V25.48 V (212.36%)695.2 WDrop/Amp High
4 AWG21.15 mm²85 A9.71 V (80.96%)2.3 V16.02 V (133.54%)437.2 WDrop/Amp High
3 AWG26.67 mm²100 A7.7 V (64.2%)4.3 V12.71 V (105.9%)346.7 WDrop/Amp High
2 AWG33.62 mm²115 A6.11 V (50.93%)5.9 V10.08 V (84.01%)275.0 WDrop/Amp High
1 AWG42.41 mm²130 A4.84 V (40.37%)7.2 V7.99 V (66.6%)218.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.84 V (32.01%)8.2 V6.34 V (52.8%)172.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.05 V (25.39%)9.0 V5.03 V (41.89%)137.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.42 V (20.14%)9.6 V3.99 V (33.22%)108.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.92 V (15.97%)10.1 V3.16 V (26.35%)86.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.62 V (13.51%)10.4 V2.67 V (22.29%)73.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.35 V (11.26%)10.6 V2.23 V (18.58%)60.8 WDrop/Amp High
350 kcmil177.3 mm²310 A1.16 V (9.66%)10.8 V1.91 V (15.93%)52.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.01 V (8.45%)11.0 V1.67 V (13.93%)45.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.81 V (6.76%)11.2 V1.34 V (11.15%)36.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.68 V (5.63%)11.3 V1.11 V (9.29%)30.4 WDrop/Amp High
750 kcmil380.0 mm²475 A0.54 V (4.51%)11.5 V0.89 V (7.43%)24.3 W~ ≤5%
1000 kcmil506.7 mm²545 A0.41 V (3.38%)11.6 V0.67 V (5.57%)18.2 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 350 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 350 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (1.69%) and delivers 11.8V at the load.

What size aluminum wire is required for 45 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.67V (5.57%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.