🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.86V (7.17%)
Voltage at Load End11.7 VLoss: 0.26 V (11.8 W)
Power & Breaker (125%)0.54 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A127.0 V (1058.37%)0.0 V209.5 V (1745.82%)5715.2 WDrop/Amp High
12 AWG3.31 mm²20 A79.81 V (665.08%)0.0 V131.65 V (1097.07%)3591.4 WDrop/Amp High
10 AWG5.26 mm²30 A50.22 V (418.52%)0.0 V82.84 V (690.36%)2260.0 WDrop/Amp High
8 AWG8.37 mm²50 A31.56 V (263.01%)0.0 V52.06 V (433.85%)1420.3 WDrop/Amp High
6 AWG13.3 mm²65 A19.86 V (165.52%)0.0 V32.76 V (273.03%)893.8 WDrop/Amp High
4 AWG21.15 mm²85 A12.49 V (104.09%)0.0 V20.6 V (171.69%)562.1 WDrop/Amp High
3 AWG26.67 mm²100 A9.91 V (82.54%)2.1 V16.34 V (136.16%)445.7 WDrop/Amp High
2 AWG33.62 mm²115 A7.86 V (65.48%)4.1 V12.96 V (108.01%)353.6 WDrop/Amp High
1 AWG42.41 mm²130 A6.23 V (51.91%)5.8 V10.27 V (85.62%)280.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.94 V (41.16%)7.1 V8.15 V (67.89%)222.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.92 V (32.65%)8.1 V6.46 V (53.85%)176.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.11 V (25.9%)8.9 V5.13 V (42.72%)139.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.46 V (20.54%)9.5 V4.06 V (33.87%)110.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.09 V (17.38%)9.9 V3.44 V (28.66%)93.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.74 V (14.48%)10.3 V2.87 V (23.89%)78.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.49 V (12.42%)10.5 V2.46 V (20.48%)67.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.3 V (10.86%)10.7 V2.15 V (17.91%)58.6 WDrop/Amp High
500 kcmil253.4 mm²380 A1.04 V (8.69%)11.0 V1.72 V (14.33%)46.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.87 V (7.24%)11.1 V1.43 V (11.95%)39.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.7 V (5.79%)11.3 V1.15 V (9.56%)31.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.52 V (4.34%)11.5 V0.86 V (7.17%)23.5 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 450 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.26V (2.17%) and delivers 11.7V at the load.

What size aluminum wire is required for 45 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.86V (7.17%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.