🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 3.0%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 5.92V (2.47%)
Voltage at Load End232.8 VLoss: 7.19 V (560.6 W)
Power & Breaker (125%)18.71 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A146.65 V (61.11%)93.3 V241.91 V (100.8%)11430.4 WDrop/Amp High
12 AWG3.31 mm²20 A92.16 V (38.4%)147.8 V152.01 V (63.34%)7182.9 WDrop/Amp High
10 AWG5.26 mm²30 A57.99 V (24.16%)182.0 V95.66 V (39.86%)4520.0 WDrop/Amp High
8 AWG8.37 mm²50 A36.44 V (15.19%)203.6 V60.12 V (25.05%)2840.5 WDrop/Amp High
6 AWG13.3 mm²65 A22.94 V (9.56%)217.1 V37.83 V (15.76%)1787.6 WDrop/Amp High
4 AWG21.15 mm²85 A14.42 V (6.01%)225.6 V23.79 V (9.91%)1124.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.44 V (4.77%)228.6 V18.87 V (7.86%)891.5 W~ ≤5%
2 AWG33.62 mm²115 A9.07 V (3.78%)230.9 V14.97 V (6.24%)707.2 W~ ≤5%
1 AWG42.41 mm²130 A7.19 V (3.0%)232.8 V11.86 V (4.94%)560.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.7 V (2.38%)234.3 V9.41 V (3.92%)444.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.52 V (1.88%)235.5 V7.46 V (3.11%)352.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.59 V (1.5%)236.4 V5.92 V (2.47%)279.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.85 V (1.19%)237.2 V4.69 V (1.96%)221.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.41 V (1.0%)237.6 V3.97 V (1.65%)187.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.01 V (0.84%)238.0 V3.31 V (1.38%)156.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.72 V (0.72%)238.3 V2.84 V (1.18%)134.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.5 V (0.63%)238.5 V2.48 V (1.03%)117.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.2 V (0.5%)238.8 V1.99 V (0.83%)93.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.0 V (0.42%)239.0 V1.66 V (0.69%)78.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.8 V (0.33%)239.2 V1.32 V (0.55%)62.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.6 V (0.25%)239.4 V0.99 V (0.41%)46.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 600 feet one-way at 240V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 7.19V (3.0%) and delivers 232.8V at the load.

What size aluminum wire is required for 45 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 5.92V (2.47%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.