🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.46%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 3.06V (2.55%)
Voltage at Load End117.0 VLoss: 2.95 V (236.2 W)
Power & Breaker (125%)9.6 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A60.21 V (50.17%)59.8 V99.32 V (82.76%)4816.8 WDrop/Amp High
12 AWG3.31 mm²20 A37.84 V (31.53%)82.2 V62.41 V (52.01%)3026.9 WDrop/Amp High
10 AWG5.26 mm²30 A23.81 V (19.84%)96.2 V39.27 V (32.73%)1904.7 WDrop/Amp High
8 AWG8.37 mm²50 A14.96 V (12.47%)105.0 V24.68 V (20.57%)1197.0 WDrop/Amp High
6 AWG13.3 mm²65 A9.42 V (7.85%)110.6 V15.53 V (12.94%)753.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.92 V (4.93%)114.1 V9.77 V (8.14%)473.7 W~ ≤5%
3 AWG26.67 mm²100 A4.7 V (3.91%)115.3 V7.75 V (6.45%)375.7 W~ ≤5%
2 AWG33.62 mm²115 A3.73 V (3.1%)116.3 V6.14 V (5.12%)298.0 W~ ≤5%
1 AWG42.41 mm²130 A2.95 V (2.46%)117.0 V4.87 V (4.06%)236.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.34 V (1.95%)117.7 V3.86 V (3.22%)187.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.86 V (1.55%)118.1 V3.06 V (2.55%)148.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.47 V (1.23%)118.5 V2.43 V (2.03%)117.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.17 V (0.97%)118.8 V1.93 V (1.61%)93.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.99 V (0.82%)119.0 V1.63 V (1.36%)79.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.82 V (0.69%)119.2 V1.36 V (1.13%)65.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.71 V (0.59%)119.3 V1.17 V (0.97%)56.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.62 V (0.51%)119.4 V1.02 V (0.85%)49.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.49 V (0.41%)119.5 V0.82 V (0.68%)39.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.41 V (0.34%)119.6 V0.68 V (0.57%)33.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.33 V (0.27%)119.7 V0.54 V (0.45%)26.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.25 V (0.21%)119.8 V0.41 V (0.34%)19.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 120 feet one-way at 120V (1-Phase), you need 1 AWG copper wire. This produces a voltage drop of 2.95V (2.46%) and delivers 117.0V at the load.

What size aluminum wire is required for 80 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 3.06V (2.55%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.