⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 50 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.45%
Aluminum Wire (≤3% Drop)2 AWGDrop: 2.22V (0.46%)
Voltage at Load End477.9 VLoss: 2.14 V (296.1 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 50 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.73 V (4.53%)458.3 V35.84 V (7.47%)3010.5 WDrop/Amp High
12 AWG3.31 mm²20 A13.65 V (2.84%)466.3 V22.52 V (4.69%)1891.8 WDrop/Amp High
10 AWG5.26 mm²30 A8.59 V (1.79%)471.4 V14.17 V (2.95%)1190.5 WDrop/Amp High
8 AWG8.37 mm²50 A5.4 V (1.12%)474.6 V8.91 V (1.86%)748.1 WDrop/Amp High
6 AWG13.3 mm²65 A3.4 V (0.71%)476.6 V5.6 V (1.17%)470.8 WDrop/Amp High
4 AWG21.15 mm²85 A2.14 V (0.45%)477.9 V3.52 V (0.73%)296.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.69 V (0.35%)478.3 V2.8 V (0.58%)234.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.34 V (0.28%)478.7 V2.22 V (0.46%)186.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.07 V (0.22%)478.9 V1.76 V (0.37%)147.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.84 V (0.18%)479.2 V1.39 V (0.29%)117.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.67 V (0.14%)479.3 V1.11 V (0.23%)92.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.53 V (0.11%)479.5 V0.88 V (0.18%)73.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.42 V (0.09%)479.6 V0.7 V (0.14%)58.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.36 V (0.07%)479.6 V0.59 V (0.12%)49.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.3 V (0.06%)479.7 V0.49 V (0.1%)41.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.25 V (0.05%)479.7 V0.42 V (0.09%)35.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.22 V (0.05%)479.8 V0.37 V (0.08%)30.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.18 V (0.04%)479.8 V0.29 V (0.06%)24.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.03%)479.9 V0.25 V (0.05%)20.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.02%)479.9 V0.2 V (0.04%)16.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.02%)479.9 V0.15 V (0.03%)12.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 50 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 50 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 2.14V (0.45%) and delivers 477.9V at the load.

What size aluminum wire is required for 80 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 2.22V (0.46%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.