🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.41V (5.17%)
Voltage at Load End236.2 VLoss: 3.77 V (2932.6 W)
Power & Breaker (125%)187.06 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1833.16 V (763.82%)0.0 V3023.85 V (1259.94%)1428805.0 WDrop/Amp High
12 AWG3.31 mm²20 A1151.95 V (479.98%)0.0 V1900.19 V (791.74%)897859.3 WDrop/Amp High
10 AWG5.26 mm²30 A724.9 V (302.04%)0.0 V1195.74 V (498.23%)565002.7 WDrop/Amp High
8 AWG8.37 mm²50 A455.55 V (189.81%)0.0 V751.45 V (313.1%)355067.4 WDrop/Amp High
6 AWG13.3 mm²65 A286.69 V (119.45%)0.0 V472.9 V (197.04%)223452.2 WDrop/Amp High
4 AWG21.15 mm²85 A180.28 V (75.12%)59.7 V297.38 V (123.91%)140516.0 WDrop/Amp High
3 AWG26.67 mm²100 A142.97 V (59.57%)97.0 V235.83 V (98.26%)111432.9 WDrop/Amp High
2 AWG33.62 mm²115 A113.41 V (47.26%)126.6 V187.08 V (77.95%)88397.2 WDrop/Amp High
1 AWG42.41 mm²130 A89.91 V (37.46%)150.1 V148.31 V (61.79%)70075.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A71.28 V (29.7%)168.7 V117.58 V (48.99%)55560.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A56.55 V (23.56%)183.5 V93.28 V (38.87%)44074.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A44.85 V (18.69%)195.1 V73.99 V (30.83%)34959.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A35.57 V (14.82%)204.4 V58.67 V (24.45%)27723.1 WDrop/Amp High
250 kcmil126.7 mm²255 A30.09 V (12.54%)209.9 V49.64 V (20.68%)23456.3 WDrop/Amp High
300 kcmil152.0 mm²285 A25.09 V (10.45%)214.9 V41.38 V (17.24%)19552.1 WDrop/Amp High
350 kcmil177.3 mm²310 A21.51 V (8.96%)218.5 V35.47 V (14.78%)16762.1 WDrop/Amp High
400 kcmil202.7 mm²335 A18.81 V (7.84%)221.2 V31.03 V (12.93%)14661.6 WDrop/Amp High
500 kcmil253.4 mm²380 A15.05 V (6.27%)225.0 V24.82 V (10.34%)11728.2 WDrop/Amp High
600 kcmil304.0 mm²420 A12.54 V (5.23%)227.5 V20.69 V (8.62%)9776.0 WDrop/Amp High
750 kcmil380.0 mm²475 A10.03 V (4.18%)230.0 V16.55 V (6.9%)7820.8 W~ ≤5%
1000 kcmil506.7 mm²545 A7.53 V (3.14%)232.5 V12.41 V (5.17%)5865.2 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 750 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.77V (1.57%) and delivers 236.2V at the load.

What size aluminum wire is required for 450 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.41V (5.17%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.