⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.34%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.87V (0.42%)
Voltage at Load End207.3 VLoss: 0.71 V (580.9 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A129.0 V (62.02%)79.0 V212.79 V (102.3%)106131.4 WDrop/Amp High
12 AWG3.31 mm²20 A81.06 V (38.97%)126.9 V133.72 V (64.29%)66692.8 WDrop/Amp High
10 AWG5.26 mm²30 A51.01 V (24.52%)157.0 V84.14 V (40.45%)41968.3 WDrop/Amp High
8 AWG8.37 mm²50 A32.06 V (15.41%)175.9 V52.88 V (25.42%)26374.3 WDrop/Amp High
6 AWG13.3 mm²65 A20.17 V (9.7%)187.8 V33.28 V (16.0%)16598.0 WDrop/Amp High
4 AWG21.15 mm²85 A12.69 V (6.1%)195.3 V20.93 V (10.06%)10437.5 WDrop/Amp High
3 AWG26.67 mm²100 A10.06 V (4.84%)197.9 V16.6 V (7.98%)8277.2 WDrop/Amp High
2 AWG33.62 mm²115 A7.98 V (3.84%)200.0 V13.16 V (6.33%)6566.1 WDrop/Amp High
1 AWG42.41 mm²130 A6.33 V (3.04%)201.7 V10.44 V (5.02%)5205.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.02 V (2.41%)203.0 V8.27 V (3.98%)4127.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.98 V (1.91%)204.0 V6.56 V (3.16%)3273.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.16 V (1.52%)204.8 V5.21 V (2.5%)2596.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.5 V (1.2%)205.5 V4.13 V (1.98%)2059.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.12 V (1.02%)205.9 V3.49 V (1.68%)1742.3 WDrop/Amp High
300 kcmil152.0 mm²285 A1.77 V (0.85%)206.2 V2.91 V (1.4%)1452.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.51 V (0.73%)206.5 V2.5 V (1.2%)1245.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.32 V (0.64%)206.7 V2.18 V (1.05%)1089.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.06 V (0.51%)206.9 V1.75 V (0.84%)871.2 WDrop/Amp High
600 kcmil304.0 mm²420 A0.88 V (0.42%)207.1 V1.46 V (0.7%)726.2 WDrop/Amp High
750 kcmil380.0 mm²475 A0.71 V (0.34%)207.3 V1.16 V (0.56%)580.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.53 V (0.25%)207.5 V0.87 V (0.42%)435.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 50 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.71V (0.34%) and delivers 207.3V at the load.

What size aluminum wire is required for 475 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.87V (0.42%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.