🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.75V (0.84%)
Voltage at Load End206.6 VLoss: 1.41 V (1161.9 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A258.0 V (124.04%)0.0 V425.58 V (204.61%)212262.8 WDrop/Amp High
12 AWG3.31 mm²20 A162.13 V (77.95%)45.9 V267.43 V (128.57%)133385.7 WDrop/Amp High
10 AWG5.26 mm²30 A102.02 V (49.05%)106.0 V168.29 V (80.91%)83936.6 WDrop/Amp High
8 AWG8.37 mm²50 A64.11 V (30.82%)143.9 V105.76 V (50.85%)52748.7 WDrop/Amp High
6 AWG13.3 mm²65 A40.35 V (19.4%)167.7 V66.56 V (32.0%)33196.0 WDrop/Amp High
4 AWG21.15 mm²85 A25.37 V (12.2%)182.6 V41.85 V (20.12%)20875.0 WDrop/Amp High
3 AWG26.67 mm²100 A20.12 V (9.67%)187.9 V33.19 V (15.96%)16554.4 WDrop/Amp High
2 AWG33.62 mm²115 A15.96 V (7.67%)192.0 V26.33 V (12.66%)13132.3 WDrop/Amp High
1 AWG42.41 mm²130 A12.65 V (6.08%)195.3 V20.87 V (10.03%)10410.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.03 V (4.82%)198.0 V16.55 V (7.96%)8254.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.96 V (3.83%)200.0 V13.13 V (6.31%)6547.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.31 V (3.03%)201.7 V10.41 V (5.01%)5193.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.01 V (2.41%)203.0 V8.26 V (3.97%)4118.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.24 V (2.04%)203.8 V6.99 V (3.36%)3484.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.53 V (1.7%)204.5 V5.82 V (2.8%)2904.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.03 V (1.46%)205.0 V4.99 V (2.4%)2490.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.65 V (1.27%)205.4 V4.37 V (2.1%)2178.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.12 V (1.02%)205.9 V3.49 V (1.68%)1742.3 WDrop/Amp High
600 kcmil304.0 mm²420 A1.77 V (0.85%)206.2 V2.91 V (1.4%)1452.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.41 V (0.68%)206.6 V2.33 V (1.12%)1161.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.06 V (0.51%)206.9 V1.75 V (0.84%)871.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 100 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.41V (0.68%) and delivers 206.6V at the load.

What size aluminum wire is required for 475 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.75V (0.84%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.