🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.54%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.4V (0.67%)
Voltage at Load End206.9 VLoss: 1.13 V (929.5 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A206.4 V (99.23%)1.6 V340.46 V (163.68%)169810.2 WDrop/Amp High
12 AWG3.31 mm²20 A129.7 V (62.36%)78.3 V213.95 V (102.86%)106708.5 WDrop/Amp High
10 AWG5.26 mm²30 A81.62 V (39.24%)126.4 V134.63 V (64.73%)67149.3 WDrop/Amp High
8 AWG8.37 mm²50 A51.29 V (24.66%)156.7 V84.61 V (40.68%)42199.0 WDrop/Amp High
6 AWG13.3 mm²65 A32.28 V (15.52%)175.7 V53.25 V (25.6%)26556.8 WDrop/Amp High
4 AWG21.15 mm²85 A20.3 V (9.76%)187.7 V33.48 V (16.1%)16700.0 WDrop/Amp High
3 AWG26.67 mm²100 A16.1 V (7.74%)191.9 V26.55 V (12.77%)13243.5 WDrop/Amp High
2 AWG33.62 mm²115 A12.77 V (6.14%)195.2 V21.06 V (10.13%)10505.8 WDrop/Amp High
1 AWG42.41 mm²130 A10.12 V (4.87%)197.9 V16.7 V (8.03%)8328.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.03 V (3.86%)200.0 V13.24 V (6.36%)6603.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.37 V (3.06%)201.6 V10.5 V (5.05%)5238.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.05 V (2.43%)202.9 V8.33 V (4.0%)4154.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.0 V (1.93%)204.0 V6.61 V (3.18%)3294.8 WDrop/Amp High
250 kcmil126.7 mm²255 A3.39 V (1.63%)204.6 V5.59 V (2.69%)2787.7 WDrop/Amp High
300 kcmil152.0 mm²285 A2.82 V (1.36%)205.2 V4.66 V (2.24%)2323.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.42 V (1.16%)205.6 V3.99 V (1.92%)1992.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.12 V (1.02%)205.9 V3.49 V (1.68%)1742.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.69 V (0.81%)206.3 V2.79 V (1.34%)1393.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.41 V (0.68%)206.6 V2.33 V (1.12%)1161.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.13 V (0.54%)206.9 V1.86 V (0.9%)929.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.85 V (0.41%)207.2 V1.4 V (0.67%)697.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 80 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.13V (0.54%) and delivers 206.9V at the load.

What size aluminum wire is required for 475 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.4V (0.67%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.