🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.53%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.48V (5.04%)
Voltage at Load End204.8 VLoss: 3.17 V (2614.0 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1548.0 V (744.23%)0.0 V2553.48 V (1227.63%)1273576.8 WDrop/Amp High
12 AWG3.31 mm²20 A972.76 V (467.67%)0.0 V1604.6 V (771.44%)800314.1 WDrop/Amp High
10 AWG5.26 mm²30 A612.14 V (294.3%)0.0 V1009.74 V (485.45%)503619.7 WDrop/Amp High
8 AWG8.37 mm²50 A384.69 V (184.95%)0.0 V634.56 V (305.07%)316492.2 WDrop/Amp High
6 AWG13.3 mm²65 A242.09 V (116.39%)0.0 V399.34 V (191.99%)199175.9 WDrop/Amp High
4 AWG21.15 mm²85 A152.24 V (73.19%)55.8 V251.12 V (120.73%)125250.1 WDrop/Amp High
3 AWG26.67 mm²100 A120.73 V (58.04%)87.3 V199.15 V (95.74%)99326.6 WDrop/Amp High
2 AWG33.62 mm²115 A95.77 V (46.04%)112.2 V157.98 V (75.95%)78793.6 WDrop/Amp High
1 AWG42.41 mm²130 A75.92 V (36.5%)132.1 V125.24 V (60.21%)62462.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A60.2 V (28.94%)147.8 V99.29 V (47.74%)49524.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.75 V (22.96%)160.2 V78.77 V (37.87%)39285.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.88 V (18.21%)170.1 V62.48 V (30.04%)31161.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A30.04 V (14.44%)178.0 V49.55 V (23.82%)24711.2 WDrop/Amp High
250 kcmil126.7 mm²255 A25.41 V (12.22%)182.6 V41.92 V (20.15%)20908.0 WDrop/Amp High
300 kcmil152.0 mm²285 A21.18 V (10.18%)186.8 V34.94 V (16.8%)17427.9 WDrop/Amp High
350 kcmil177.3 mm²310 A18.16 V (8.73%)189.8 V29.96 V (14.4%)14941.0 WDrop/Amp High
400 kcmil202.7 mm²335 A15.88 V (7.64%)192.1 V26.2 V (12.6%)13068.8 WDrop/Amp High
500 kcmil253.4 mm²380 A12.71 V (6.11%)195.3 V20.96 V (10.08%)10454.0 WDrop/Amp High
600 kcmil304.0 mm²420 A10.59 V (5.09%)197.4 V17.47 V (8.4%)8713.9 WDrop/Amp High
750 kcmil380.0 mm²475 A8.47 V (4.07%)199.5 V13.98 V (6.72%)6971.2 W~ ≤5%
1000 kcmil506.7 mm²545 A6.35 V (3.06%)201.6 V10.48 V (5.04%)5228.0 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 600 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.17V (1.53%) and delivers 204.8V at the load.

What size aluminum wire is required for 475 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.48V (5.04%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.