⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 100 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)2 AWGDrop: 0.32V (2.67%)
Voltage at Load End11.7 VLoss: 0.31 V (1.5 W)
Power & Breaker (125%)0.06 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 100 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3.14 V (26.13%)8.9 V5.17 V (43.11%)15.7 WDrop/Amp High
12 AWG3.31 mm²20 A1.97 V (16.42%)10.0 V3.25 V (27.09%)9.9 WDrop/Amp High
10 AWG5.26 mm²30 A1.24 V (10.33%)10.8 V2.05 V (17.05%)6.2 WDrop/Amp High
8 AWG8.37 mm²50 A0.78 V (6.49%)11.2 V1.29 V (10.71%)3.9 WDrop/Amp High
6 AWG13.3 mm²65 A0.49 V (4.09%)11.5 V0.81 V (6.74%)2.5 W~ ≤5%
4 AWG21.15 mm²85 A0.31 V (2.57%)11.7 V0.51 V (4.24%)1.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.24 V (2.04%)11.8 V0.4 V (3.36%)1.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.19 V (1.62%)11.8 V0.32 V (2.67%)1.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.15 V (1.28%)11.8 V0.25 V (2.11%)0.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.12 V (1.02%)11.9 V0.2 V (1.68%)0.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.1 V (0.81%)11.9 V0.16 V (1.33%)0.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.08 V (0.64%)11.9 V0.13 V (1.05%)0.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.06 V (0.51%)11.9 V0.1 V (0.84%)0.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.05 V (0.43%)11.9 V0.08 V (0.71%)0.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.04 V (0.36%)12.0 V0.07 V (0.59%)0.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.04 V (0.31%)12.0 V0.06 V (0.51%)0.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.03 V (0.27%)12.0 V0.05 V (0.44%)0.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.03 V (0.21%)12.0 V0.04 V (0.35%)0.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.02 V (0.18%)12.0 V0.04 V (0.29%)0.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.02 V (0.14%)12.0 V0.03 V (0.24%)0.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.11%)12.0 V0.02 V (0.18%)0.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 100 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 100 feet one-way at 12V (DC), you need 4 AWG copper wire. This produces a voltage drop of 0.31V (2.57%) and delivers 11.7V at the load.

What size aluminum wire is required for 5 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 0.32V (2.67%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.